DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Function Group

RUN/STOP Switch

Number

M1035

Contents:

 

When M1035 = ON, PLC uses input point X7 as the switch of RUN/STOP.

Function Group COM Port Function

 

 

 

 

 

 

 

 

 

Port

COM1

COM2

COM3

 

Item

 

 

 

 

Number

Communication format

D1036

D1120

D1109

 

 

 

 

Communication setting holding

M1138

M1120

M1136

 

 

 

 

 

 

 

ASCII/RTU mode

M1139

M1143

M1320

 

 

 

 

 

 

Slave communication address

D1121

D1255

 

 

 

 

 

Contents:

COM ports (COM1: RS-232, COM2: RS-485, COM3: RS-485) support communication format of MODBUS ASCII/RTU modes. When RTU format is selected, the data length should be set as 8. COM2 and COM3 support transmission speed up to 921kbps. COM1, COM2 and COM3 can be used at the same time.

COM1:

Can be used in master or slave mode. Supports ASCII/RTU communication format, baudrate (115200bps max), and modification on data length (data bits, parity bits, stop bits). D1036: COM1 (RS-232) communication protocol of master/slave PLC. (b8 - b15 are not used) Please refer to table below for setting.

COM2:

Can be used in master or slave mode. Supports ASCII/RTU communication format, baudrate (921kbps max), and modification on data length (data bits, parity bits, stop bits). D1120: COM2 (RS-485) communication protocol of master/slave PLC. Please refer to table below for setting.

COM3:

Can be used in master or slave mode. Supports ASCII/RTU communication format, baudrate (921kbps max), and modification on data length (data bits, parity bits, stop bits). D1109: COM3 (RS-485) communication protocol of master/slave PLC. (b8 - b15 are not used) Please refer to table below for setting.

 

 

Content

 

b0

Data Length

0: 7 data bits, 1: 8 data bits

(RTU supports 8 data bits only)

 

 

b1

 

00: None

 

Parity bit

01: Odd

 

b2

 

 

11: Even

 

 

 

 

b3

Stop bits

0: 1 bit, 1: 2bits

 

b4

Baud rate

0001(H1):

110

b5

 

0010(H2):

150

b6

 

0011(H3):

300

2 - 62

 

 

 