DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

 

Y3

 

 

 

 

 

 

 

 

Pulse

 

Dir

 

 

 

 

 

 

 

 

 

 

 

 

58.

When assigning Y0 and Y2 output mode as Pulse, i.e. D1220 = K0, D1221 = K0, the available

 

range for S2 is 1~32,767 (16-bit instruction) and 1~2,147,483,647 (32-bit instruction).

59.

When assigning Y0 and Y2 output mode as Pulse/Dir, i.e. D1220 = K1, D1221 = K1, the

 

available range for S2 is 1~32,767 or -1~-32,768 (16-bit instruction) and 1~2,147,483,647 or

 

-1~-2,147,483,648 (32-bit instruction)

 

 

 

 

 

 

60.

When assigning output device as Y1 and Y3, the available range for S2 is 1~32,767 (16-bit

 

instruction) and 1~2,147,483,647 (32-bit instruction).

 

 

 

61.

S3: Ramp up/down time (unit: ms, min. 20ms).

 

 

 

 

 

 

 

When assigning output device as Y1 and Y3, the set value of ramp up and ramp down time

 

should be the same.

 

 

 

 

 

 

 

 

 

 

When assigning output device as Y0 and Y2, and if:

 

 

 

 

„ M1348 = OFF (Y0) and M1535 = OFF (Y2), the ramp up and ramp down time should be

 

the same.

 

 

 

 

 

 

 

 

 

 

„ M1348 = ON and M1535 = ON, then S3 specifies ramp up time only. The ramp down time

 

is specified by value set in D1348 (Y0) and D1349 (Y2).

 

 

 

62.

When M1257 = OFF, ramp up/down curve of Y0 and Y2 is straight line. When M1257 = ON,

 

ramp up/down curve will be S curve. The ramp up/down curve of Y1 and Y3 is fixed as straight

 

line

 

 

 

 

 

 

 

 

 

63.

The output will not be affected if S1, S2 or S3 are changed when PLSR instruction is being

 

executed. PLSR instruction has to be stopped if changing values in S1, S2 or S3 is required.

64.

Flags for indicating pulse output status:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

Y0

 

Y1

 

Y2

 

Y3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Completion

 

M1029

 

M1030

 

M1102

 

M1103

 

 

 

 

 

 

 

 

 

 

 

Immediately Pause

 

M1078

 

M1079

 

M1104

 

M1105

 

 

 

 

 

 

 

a) When pulse output on Y0/Y1 specified as Pulse/Dir (D1220 = K1) is completed,

 

completion flag M1029 = ON.

 

 

 

 

 

 

 

b) When pulse output on Y2/Y3 specified as Pulse/Dir (D1221 = K1) is completed,

 

completion flag M1102 = On

 

 

 

 

 

 

 

c) When PLSR/DPLSR instruction is activated again, the completion flags will automatically

 

be reset.

 

 

 

 

 

 

 

 

 

65.

During the ramp up process, the pulse numbers (frequency x time) of each speed shift may not

 

all be integer values, but PLC will operate integer value only. In this case, the omitted decimals

 

will result in errors between each speed shift, i.e. pulse number for each shift may differ due to

this operation. For ensuring the required output pulse number, PLC will fill in pulses as need automatically in order to correct the deviation.

3 - 146