DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

2.By using PLC-Link, D1038 can be set to send next communication data with delay. Unit: 1 scan cycle. 0~10,000 adjustable

Function Group

Fixed scan time

Number

M1039, D1039

Contents:

 

1.When M1039 is ON, program scan time is determined by D1039. When program execution is completed, next scan will be activated only when the fixed scan time is reached. If D1039 is less than actual scan time, it will scan by the actual program scan time.

 

M1000

 

 

 

 

 

 

 

M1039

Fix scan time

 

normally ON

 

 

 

 

 

 

 

 

 

contact

MOV

P

K20 D1039

Scan time is fixed to 20ms

2.Instructions related to scan time, RAMP, HKY, SEGL, ARWS and PR should be used with “fixed scan time” or “timed interrupt”.

3.Particularly for instruction HKY, which is applied for 16-keys input operated by 4x4 matrix, scan time should be set to 20ms or above.

4.Scan time displayed in D1010~D1012 also includes fixed scan time.

Function Group Analog Function built in the PLC

Number

D1062, D1110~D1113, D1116~D1118

Contents:

 

1.The function is for EX2/SX2 Only

2.Resolution of AD (analog input) channels: 12 bits for 20EX2 and 20SX2; 16 bits for the voltage/current mode of 30EX2; 0.1 for the temperature mode of 30EX2

3.

The analog input signals and their corresponding digital values:

 

 

 

Model

20EX2/SX2

30EX2

 

Mode

 

 

 

 

 

 

 

-10 V~+10 V

-2000~+2000

-32000~+32000

 

Voltage

-5 V~+5 V

Not support

-32000~+32000

 

 

+1 V~+5 V

Not support

+0~+32000

 

Current

-20 mA~+20 mA

-2000~+2000

-32000~+32000

 

+4 mA~+20 mA

+0~+2000

+0~+32000

 

 

 

 

PT100/PT1000

Not support

-1800~+8000

 

 

-180 ~+800

 

Temperature

 

 

 

NI100/NI1000

 

 

 

 

Not support

-800~+1700

 

 

-80 ~ +170

 

 

 

 

4.Resolution of DA (analog output) channels: 12 bits

2 - 66

Page 98
Image 98