3. Instruction Set

32.There is no limitation on the times of using this instruction, however the program allows only 4 instructions (PLSY, PWM, PLSR) to be executed at the same time. If Y1 is used for several high speed pulse output instructions, PLC will output according to the execution order of these instructions.

Program Example:

33.When X0 = ON, 200 pulses of 1kHz are generated from output Y0, after the pulse output has been completed, M1029 = ON to set Y20.

34.When X0 = OFF, pulse output Y0 will immediately stop. When X0 turns ON again, the pulse output will start from the first pulse.

X0

PLSY K1000 K200 Y0

M1029

Y20

0.5ms

Output Y0

Points to note:

1

1ms

2

3

200

35.Description of associated flags:

M1029: M1029 = ON when Y0 pulse output is completed.

M1030: M1030 = ON when Y1 pulse output is completed.

M1102: M1102 = ON when Y2 pulse output is completed.

M1103: M1103 = ON when Y3 pulse output is completed.

M1078: Y0 pulse output pause (immediately)

M1079: Y1 pulse output pause (immediately)

M1104: Y2 pulse output pause (immediately)

M1105: Y3 pulse output pause (immediately)

M1190 Se t Y0 high speed output as 0.01~10Hz. (DVP-SE does not support this function.)

M1191 Se t Y1 high speed output as 0.01~10Hz. (DVP-SE does not support this function.)

M1192 Se t Y2 high speed output as 0.01~10Hz. (DVP-SE does not support this function.)

M1193 Se t Y3 high speed output as 0.01~10Hz. (DVP-SE does not support this function.)

M1347: Auto reset Y0 when high speed pulse output completed

3 - 1 3 9