7 CANopen Function and Operation

—Type: In SDO response message, 43 (Hex) refers to reading 4 bytes of data; 4B (Hex) refers to reading 2 bytes of data; 4F (Hex) refers to reading 1 byte of data; 60 (Hex) refers to writing 1/2/4 byte(s) of data; 80 (Hex) refers to stopping SDO command.

Example 1: Write 010203E8 (hex) to (Index_subindex) 2109_0 of slave of No. 3 through SDO and the data type of (Index_subindex) 2109_0 is double words (32 bits).

‹Request data:

 

PLC device

 

Request message

 

 

High byte(Hex)

Low byte(Hex)

 

 

 

 

D6250

Message

ReqID=01

Command =01

 

D6251

Reserved =0

Size =8

 

Header

 

 

 

 

 

D6252

Type =02

Node ID =03

 

 

 

 

 

 

 

 

D6253

 

Main index high byte =21

Main index low byte =09

 

D6254

Message

Reserved =0

Subindex =0

 

D6255

data

Datum 1=03

Datum 0=E8

 

 

 

 

 

 

D6256

 

Datum 3=01

Datum 2=02

‹ Response data:

 

 

 

PLC device

 

Response message

 

High byte(Hex)

Low byte(Hex)

 

 

D6000

Message

ResID =01

Command =01

 

 

 

D6001

Reserved =0

Size =4

Header

 

 

 

D6002

Type =60

Node ID =03

 

D6003

 

Main index high byte =21

Main index low byte =09

 

 

 

 

D6004

Message

Reserved =0

Subindex =0

D6005

data

Datum 1=00

Datum 0=00

D6006

 

Datum 3=00

Datum 2=00

 

 

 

 

Example 2: Read the value of (Index_subindex) 2109_0 of slave of No. 3 through SDO and the data type of (Index_subindex) 2109_0 is double words (32 bits).

‹Request data:

PLC device

 

Request message

 

High byte(Hex)

Low byte(Hex)

 

 

D6250

Message

ReqID =01

Command =01

 

 

 

D6251

Reserved =0

Size =4

Header

 

 

 

D6252

Type =01

Node ID =03

 

 

 

 

 

D6253

 

Main index high byte =21

Main index low byte =09

 

 

 

 

D6254

Message

Reserved =0

Subindex =0

D6255

data

Datum 1=0

Datum 0=0

 

 

 

 

D6256

 

Datum 3=0

Datum 2=0

 

 

 

 