DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

2.12 High-speed Counters

There are two types of high speed counters provided including Software High Speed Counter (SHSC) and Hardware High Speed Counter (HHSC). The same Input point (X) can be designated with only one high speed counter. Double designation on the same input or the same counter will result in syntax error when executing DCNT instruction.

Applicable Software High Speed Counters:

X

C

 

 

 

1-phase input

 

 

 

2 phase 2 input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C235

C236

C237

C238

C239

C240

C241

C242

C232

C233

C234

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X0

 

U/D

 

 

 

 

 

 

 

 

A

 

 

X1

 

 

U/D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

U/D

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X3

 

 

 

 

 

U/D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X4

 

 

 

 

 

 

U/D

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X5

 

 

 

 

 

 

 

U/D

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X6

 

 

 

 

 

 

 

 

U/D

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X7

 

 

 

 

 

 

 

 

 

U/D

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

R/F

 

M1270

M1271

M1272

M1273

M1274

M1275

M1276

M1277

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

U/D

 

M1235

M1236

M1237

M1238

M1239

M1240

M1241

M1242

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

U: Count up

D: Count down

A: Phase A input

B: Phase B input

 

 

Note:

1.U/D (Count up/Count down) can be specified by special M. OFF = count up; ON = count down.

2.R/F (Rising edge trigger/ Falling edge trigger) can also be specified by special M. OFF = Rising; ON = Falling.

3.SHSC supports max 10kHz input pulse on single point. Max 8 counters are applicable in the same time.

4.SS2 model does not support 2-phase 2-input conuting by (X0,X2) (C232).

5.For 2-phase 2-input conuting, (X4, X5) (C233) and (X6, X7) (C234), max 5kHz. (X0,X2) (C232), max 15kHz.

6.2-phase 2-input counting supports double and quadruple frequency, which is selected in D1022 as the table in next page

2 - 34

Page 66
Image 66
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual High-speed Counters, Applicable Software High Speed Counters