DVP - ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

10.Operation flow chart:

Set starting reference of the Slave PLC to be read: D1355~D1370

Set data length for reading from Slave PLC: D1434~D1449

Set starting reference of the Slave PLC to be written: D1450~D1465 Set data length for writing in Slave PLC

(PLC will take default or previous setting as the set value if these registers are not specified)

EnableM1355

M1355 = ON, auto-detection disabled. Set the Slave to be linked by M1360~ M1375 manually

Disable

M1350=OFF, Slave ID auto-detection enabled

Enable

Communication by

Disable

 

Modbus 0X17 function

 

SET M1354

 

RST M1354

Enable auto mode

Manual / Auto mode

Enable manual mode

 

 

 

EASY PLC LINK

 

SET M1351

 

SET M1352

 

 

Set times of polling

 

 

cycle (D1431)

SET M1350

Start to execute EASY PLC LINK

11.Example 1: Connect 1 Master and 2 Slaves by RS-485 and exchange 16 data between Master and Slaves through PLC LINK

a)Write the ladder diagram program into Master PLC (ID#17)

2 - 80

Page 112
Image 112
Delta DVP-ES2/EX2/SS2/SA2/SX2/SE manual Operation flow chart