DVP - ES2/EX2/SS2/SA2/SX2 Operation Manual - Programming

= D0 K1

DPPMR

D200

D202

K100000

Y0

= D0

K2

DPPMR

D204

D206

K100000

Y0

= D0

K3

DPPMR

D208

D210

K100000

Y0

= D0

K4

DPPMR

D212

D214

K100000

Y0

M0

 

 

RST

M1029

 

 

 

 

 

 

 

 

 

 

 

 

MOV

K1

D0

 

 

M0

M1029

INCP

D0

 

 

 

 

 

 

 

 

 

 

 

 

END

 

 

 

 

3.Operation:

When PLC runs and M0 = ON, PLC will start the first point-to-point motion by 100KHz. D0 will plus 1 whenever a point-to-point motion is completed and the second point-to-point motion will start to execute automatically. The operation pattern repeats until the fourth point-to-point motion is completed.

Points to note:

Associated flags and registers:

M1029: CH0 (Y0, Y1) pulse output execution completed

D1030: Present number of Y0 output pulses (HIGH WORD).

D1031: Present number of Y1 output pulses (LOW WORD).

D1336: Present value of Y2 pulse output. D1336 (High word)

D1337: Present value of Y2 pulse output. D1337(Low word)

D1340: Start/end frequency of pulse output CH0 (Y0), CH1(Y2) for DPPMR/DPPMA instruction

D1343: Ramp up/down time of pulse output CH0 (Y0), CH1(Y2) for DPPMR/DPPMA instruction

3 - 426