DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming

Device

Function

Setup Range

Explanation

No.

 

 

 

 

 

2: Reverse control (E = PV - SV).

 

 

3: Auto-tuning of parameter exclusively for the temperature

 

 

control. The device will automatically become K4 when

 

 

the auto-tuning is completed and KP, KI and KD is set with

 

 

appropriate value (not avaliable in the 32-bit instruction).

 

 

4: Exclusively for the adjusted temperature control (not

 

 

avaliable in the 32-bit instruction).

 

 

5: Automatic mode with MV upper/lower bound control.

 

 

When MV reaches upper/lower bound, the accumulation

 

 

of integral value stops.

 

 

10: TI / TD mode with MV upper/lower bound control. When

 

 

MV reaches upper/lower bound, the accumulation of

 

 

integral value stops.

 

 

 

 

 

 

 

E = the error between SV and PV. If S3

S3+5:

Tolerable range for

0~32,767

+5 is set as 5, when E is between -5

 

and 5, E will be 0. When S3 +5 = K0,

 

error (E)

 

 

 

 

the function will not be enabled.

 

 

 

 

 

 

 

Ex: if S3+6 is set as 1,000, MV will be

 

Upper bound of

 

1,000 when it exceeds 1,000. S3+6 has

S3+6:

-32,768~32,767

to be bigger or equal to

 

 

output value (MV)

 

S3+7, otherwise the upper bound and

 

 

 

 

 

 

lower bound value will switch.

 

 

 

 

S3+7:

Lower bound of

-32,768~32,767

Ex: if S3+7 is set as -1,000, MV will be

 

-1,000 when it is smaller than -1,000..

 

output value (MV)

 

 

 

 

 

 

 

 

Ex: if S3+8 is set as 1,000, the integral

 

 

 

value will be 1,000 when it is bigger

S3+8:

Upper bound of

-32,768~32,767

than 1,000 and the integration will

 

stop. S3+8 has to be bigger or equal S3

 

integral value

 

 

 

 

+9; otherwise the upper bound and

 

 

 

lower bound value will switch

 

 

 

 

 

 

 

Ex: if S3+9 is set as -1,000, the integral

S3+9:

Lower bound of

-32,768~32,767

value will be -1,000 when it is smaller

 

than -1,000 and the integration will

 

integral value

 

 

 

 

stop.

 

 

 

 

3 - 242

Page 358
Image 358