Bryant 580J*04--12 Orifice Replacement, LED Error Code Description, Gas Valves, Single Stage

Models: 580J*04--12

1 73
Download 73 pages 806 b
Page 28
Image 28
Table 8 – LED Error Code Description*

580J

Table 8 – LED Error Code Description*

LED INDICATION

ERROR CODE

DESCRIPTION

 

 

 

ON

Normal Operation

 

 

OFF

Hardware Failure

 

 

1 Flash{

Evaporator Fan On/Off Delay Modified

 

 

2 Flashes

Limit Switch Fault

 

 

3 Flashes

Flame Sense Fault

 

 

4 Flashes

4 Consecutive Limit Switch Faults

 

 

5 Flashes

Ignition Lockout Fault

 

 

6 Flashes

Induced--- Draft Motor Fault

 

 

7 Flashes

Rollout Switch Fault

 

 

8 Flashes

Internal Control Fault

 

 

9 Flashes

Software Lockout

 

 

LEGEND

LED --- Light Emitting Diode

*A 3--- second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence.

{Indicates a code that is not an error. The unit will continue to operate when this code is displayed.

IMPORTANT: Refer to Troubleshooting Table 13 and Table 14 for additional information.

Orifice Replacement

This unit uses orifice type LH32RFnnn (where nnn indicates orifice reference size). When replacing unit orifices, order the necessary parts via RCD. See Table 10 for available orifice sizes. See Table 11 and Table 12 for orifice sizes for Natural Gas and LP fuel usage at various elevations above sea level.

Check that each replacement orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum value. See Fig. 32.

Single Stage

2 Stage

C08210

Fig. 37 - Gas Valves