Bryant 580J*04--12 FIOP Smoke Detector Wiring and Response, Return Air Sensor Operating Position

Models: 580J*04--12

1 73
Download 73 pages 806 b
Page 18
Image 18
Fig. 22 - Return Air Sensor Operating Position

580J

tion of the flexible tubing to the sampling tube is the same.

C08127

Fig. 22 - Return Air Sensor Operating Position

FIOP Smoke Detector Wiring and Response

All units: FIOP smoke detector is configured to automatically shut down all unit operations when smoke

condition is detected. See Fig. 23, Smoke Detector Wiring.

Highlight A: JMP 3 is factory-cut, transferring unit control to smoke detector.

Highlight B: Smoke detector NC contact set will open on smoke alarm condition, de-energizing the ORN conductor.

Highlight C: 24-v power signal via ORN lead is removed at Smoke Detector input on LCTB; all unit operations cease immediately.

Using Remote Logic: Five conductors are provided for field use (see Highlight D) for additional annunciation functions.

Additional Application Data — Refer to Catalog No. HKRNKA-1XA for discussions on additional control features of these smoke detectors including multiple unit coordination. See Fig. 23.

B

C

FIOP Smoke Detector Wiring and Response D

A

C08435

Fig. 23 - Typical Smoke Detector System Wiring