Bryant 580J*04--12 appendix Smoke Detectors, System, Sensor, Controller Assembly

Models: 580J*04--12

1 73
Download 73 pages 806 b
Page 16
Image 16
SMOKE DETECTORS

SMOKE DETECTORS

Smoke detectors are available as factory-installed options on 580J models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements.

System

580J

The smoke detector system consists of a four-wire

controller and one or two sensors. Its primary function is

 

 

to shut down the rooftop unit in order to prevent smoke

 

from circulating throughout the building. It is not to be

 

 

used as a life saving device.

Sensor

The sensor (see Fig. 17) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube (when used) and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs (for Power, Trouble, Alarm and Dirty) and a manual test/reset button (on the left-side of the housing).

Controller

The controller (see Fig. 16) includes a controller housing, a printed circuit board, and a clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. The controller has three LEDs (for Power, Trouble and Alarm) and a manual test/reset button (on the cover face).

Duct smoke sensor

 

controller

 

Conduit nuts

 

(supplied by installer)

 

Conduit support plate

 

Terminal block cover

Controller housing

Cover gasket

Duct smoke sensor

System Exhaust tube

Exhaust gasket

Sensor housing and electronics

See

Detail A

Intake Sensor gasket

TSD-CO2 (ordering option)

Controller Plug

Sampling tube

Fig. 16 - Controller Assembly (ordered separately)

Coupling

Detail A

Magnetic test/reset switch

Alarm

Power

Trouble

Dirty

Cover gasket

Fig. 17 - Smoke Detector Sensor (ordering option)

Manual background Sensor cover

and electronics

(ordering option)

Conduit couplings

Controller cover

 

(supplied by installer)

 

 

Fastener

 

(2X)

 

Trouble

Alarm

Power

 

Test/reset

 

switch

C08208

Fig. 16 - Controller Assembly

C08209

Fig. 17 - Smoke Detector Sensor

Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc.

The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions,