Bryant 580J*04--12 appendix Troubleshooting Heating System, cont. - Altitude Compensation* A08-A12

Models: 580J*04--12

1 73
Download 73 pages 806 b
Page 31
Image 31
Table 11 (cont.) - Altitude Compensation* (A08-A12)

Table 11 (cont.) - Altitude Compensation* (A08-A12)

ELEVATION

125,000

250,000

180,000, 224,000

BTUH Nominal

BTUH Nominal

BTUH Nominal

ft (m)

NG Orifice

LP Orifice

NG Orifice

LP Orifice

NG Orifice

LP Orifice

 

 

Size

Size

Size

Size

Size

Size

0 --- 2000 (610)

311

493

†30

463

311

483

2000

(610)

321

503

†30

473

321

493

3000

(914)

321

503

311

473

321

493

4000 (1219)

331

503

311

483

331

493

5000 (1524)

331

514

311

483

331

503

6000 (1829)

341

514

311

483

341

503

7000 (2134)

351

514

321

493

351

503

8000 (2438)

361

524

331

493

361

514

9000 (2743)

372

524

341

503

372

514

10000

(3048)

382

524

351

503

382

524

11000

(3353)

392

534

361

514

392

524

12000

(3658)

†41

534

372

514

†41

534

13000

(3962)

†42

544

382

524

†42

534

14000

(4267)

†43

544

†40

534

†43

544

Table 12 – Altitude Compensation* (04-06) - Low NOx Units

ELEVATION

60,000, 90,000

120,000

 

BTUH Nominal

BTUH Nominal

ft (m)

NG Orifice Size

LP Orifice Size

NG Orifice Size

LP Orifice Size

 

 

0 --- 2000 (610)

382

534

321

503

2000

(610)

392

544

331

514

3000

(914)

†40

544

341

514

4000 (1219)

†41

544

351

514

5000 (1524)

†41

544

351

514

6000 (1829)

†42

544

361

524

7000 (2134)

†42

544

361

524

8000 (2438)

†43

554

372

524

9000 (2743)

†43

554

382

534

10000

(3048)

442

554

†40

534

11000

(3353)

442

554

†41

534

12000

(3658)

452

†56

†42

544

13000

(3962)

473

†56

†43

544

14000

(4267)

483

†56

†43

554

LEGEND:

 

NG = Natural Gas LP = Liquid Propane

1 = CRLPELEV001A00

* As the height above sea level increases, there is less oxygen per cubic

2 = CRLPELEV002A00

ft. of air. Therefore, heat input rate should be reduced at higher altitudes.

3 = CRLPELEV003A00

{ Not included in kit. May be purchased separately through dealer.

4 = CRLPELEV004A00

580J

Minimum heating entering air temperature

When operating on first stage heating, the minimum temperature of air entering the dimpled heat exchanger is 50_F continuous and 45_F intermittent for standard heat

setpoint. Indoor comfort may be compromised when heating is initiated using low entering air temperatures with insufficient heating temperature rise.

Thermostat

LCTB

exchangers and 40_F continuous and 35_F intermittent for stainless steel heat exchangers. To operate at lower mixed-air temperatures, a field-supplied outdoor-air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation. Wire the outdoor-air thermostat (part no. HH22AG106) in series with the second stage gas valve as shown below. Set the outdoor-air thermostat at 35_F for stainless steel heat

TH1

TH2

W1

OALT

W2

C08442

exchangers or 45_F for standard heat exchangers. This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat

Troubleshooting Heating System

Refer to Table 13 and Table 14 for additional troubleshooting topics.

31

Page 31
Image 31
Bryant 580J*04--12 appendix Troubleshooting Heating System, cont. - Altitude Compensation* A08-A12