Bryant 580J*04--12 appendix EonoMi$er IV Control, Indoor Air Quality IAQ Sensor Input

Models: 580J*04--12

1 73
Download 73 pages 806 b
Page 39
Image 39
Fig. 50 - EonoMi$er IV Control

N1

 

 

EXH

TR

TR1

 

N

 

Set

 

 

 

2V

10V

 

 

 

 

 

 

P1

 

EXH

 

24

24 Vac

 

 

 

Vac

COM

 

P

 

 

 

 

Min

HOT

_

T1

 

 

Pos

+

 

 

 

T

Open

 

 

 

DCV

1

2

 

 

Max

 

 

 

 

 

2V

10V

 

 

AQ1

DCV

 

 

5

 

 

 

 

 

 

 

AQ

 

DCV

 

4

SO+

 

Set

3

SO

2V

10V

 

 

 

 

 

 

SR+

Free

 

EF

EF1

 

Cool

 

 

 

SR

B

C

 

 

 

A

D

 

 

C06038

Fig. 50 - EonoMi$er IV Control

Indoor Air Quality (IAQ) Sensor Input

The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct.

Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined setpoint. (See Fig. 51.)

CO2 SENSOR MAX RANGE SETTING

 

6000

 

 

 

 

 

 

(ppm)

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

2

3

4

5

6

7

8

 

DAMPER VOLTAGE FOR MAX VENTILATION RATE

C06039

Fig. 51 - CO2 Sensor Maximum Range Settings

If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged.

When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.

When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Exhaust Setpoint Adjustment

The exhaust setpoint will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The setpoint is modified with the Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig. 45.) The setpoint represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.

Minimum Position Control

There is a minimum damper position potentiometer on the EconoMi$er IV controller. (See Fig. 45.) The minimum damper position maintains the minimum airflow into the building during the occupied period.

When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation.

When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise.

Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10_F temperature difference between the outdoor and return-air temperatures.

To determine the minimum position setting, perform the following procedure:

1.Calculate the appropriate mixed air temperature using the following formula:

(TO x 100OA ) + (TR x 100RA ) =TM

TO = Outdoor-Air Temperature

OA = Percent of Outdoor Air

TR = Return-Air Temperature

RA = Percent of Return Air

TM = Mixed-Air Temperature

As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60_F, and return-air temperature is 75_F.

(60 x .10) + (75 x .90) = 73.5_F

2.Disconnect the supply air sensor from terminals T and T1.

3.Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 41 and that the minimum position potentiometer is turned fully clockwise.

4.Connect 24 vac across terminals TR and TR1.

580J

39

Page 39
Image 39
Bryant 580J*04--12 appendix EonoMi$er IV Control, Indoor Air Quality IAQ Sensor Input, CO2 Sensor Maximum Range Settings