Emerson GXT2U user manual Output Voltage Selection

Page 20

Output Voltage Selection

The Output Voltage is user configurable and is designed to allow selecting or changing the desired output voltage to match the utility via the Liebert GXT2U Configuration Program provided with the UPS. The settings to choose from are 200, 208, 220, 230, and 240 VAC output. The factory default setting is 208 VAC.

! CAUTION

Never change the voltage settings while the UPS is ON and powering connected loads.

NOTE

Setting output voltage to 200 VAC will cause the UPS unit to be derated to 2400 VA, 1680 watts.

16

DISCONTINUED

PRODUCT

 

Image 20
Contents Liebert GXT2U DIS Product Table of Contents Operating Instructions Important Safety Instructions DIS Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerMajor Components Transient Voltage Surge Suppression and EMI/RFI FiltersDynamic Bypass BatteryDC-to-DC Converter Liebert GXT2U-Rear View Installation Tower UPS InstallationPreparation Base to accommodateRack-Mount UPS Conversion and Installation Optional rack mount handlesMounting rails M5 screwsApply grease UPS or battery cabinet Apply grease inside External Battery Cabinet Installation DIS Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonLoad/Battery Level Indicators 4 Green, 1 Amber Fault Indicator LED RedBypass Indicator LED Amber UPS on Indicator LED GreenOutput Voltage Selection Operating Instructions Normal Mode OperationBypass Mode Operation Battery Mode Operation Battery Recharge ModePins 4 & 5 Remote Shutdown on Battery CommunicationsCommunications Interface Port Pin Assignment DescriptionPins 5 & 6 Any-Mode Shutdown Auto-Enable Output Pin 6 LogicUPS Intelligent Communications Configuration Program Liebert GXT2U Configuration Program AbilitiesMaintenance Battery ReplacementInternal Battery Replacement Procedures Troubleshooting On bypass due to overtemperature condition beep every 4 secOn bypass due to DC bus overvoltage beep every 4 sec On bypass due to PFC failure beep every 4 secTroubleshooting Guide Problem Cause SolutionBattery test is performed Alarm Conditions Condition AlarmSpecifications WEIGHT, lb kg Battery Cabinet SpecificationsDimensions in mm Battery Run Times Internal BatteryLoad % MinutesProduct Warranty Registration DIS DIS DIS Product Locations Technical Support / ServiceEmerson Network Power
Related manuals
Manual 40 pages 63.98 Kb