Emerson GXT2U Troubleshooting, On bypass due to overtemperature condition beep every 4 sec

Page 29

TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the Liebert GXT2U develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.The Fault indicator will illuminate, indicating the UPS detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional load/battery level LED indicators will be illumi- nated to provide a diagnostic aid to the operator, as described below:

Fault

E

BYPASS

D

C

UPS ON

 

B BATTERY

A

AC

INPUT

This example shows the UPS

on bypass due to output overload.

A B C D E Fault

AC INPUT BATTERY UPS ON BYPASS

LOAD/BATTERY

LEVEL INDICATORS

LED

Diagnosis/Audible alarm

Status

 

 

 

All LEDs

On bypass due to output overload; beep every half-second

A LED

On bypass due to overtemperature condition; beep every 4 sec.

B LED

On bypass due to DC bus overvoltage; beep every 4 sec.

C LED

On bypass due to control power supply failure; beep every 4 sec.

D LED

On bypass due to PFC failure; beep every 4 sec.

E LED

On bypass due to inverter failure; beep every 4 sec.

A&C LEDs

UPS failed battery test; long beep every minute

C&E LEDs

UPS shutdown due to command from communication port (SNMP); no beep

Battery LED

Internal Battery source not available (continuous horn). Check battery

Flashing

connection, completely power down and reboot UPS.

AC LED

Line-to-neutral reversal in the AC input power supply or a loss of proper

Flashing

grounding; continuous horn and UPS will not start.

Bypass LED

Utility power voltage or frequency is out of tolerance; bypass is unavailable.

Flashing

 

Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational.

If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.

25

DISCONTINUED

PRODUCT

 

Image 29
Contents Liebert GXT2U DIS Product Table of Contents Operating Instructions Important Safety Instructions DIS Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitMajor Components Transient Voltage Surge Suppression and EMI/RFI FiltersDynamic Bypass BatteryDC-to-DC Converter Liebert GXT2U-Rear View Tower UPS Installation InstallationPreparation Base to accommodateOptional rack mount handles Rack-Mount UPS Conversion and InstallationM5 screws Mounting railsApply grease UPS or battery cabinet Apply grease inside External Battery Cabinet Installation DIS ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsFault Indicator LED Red Load/Battery Level Indicators 4 Green, 1 AmberBypass Indicator LED Amber UPS on Indicator LED GreenOutput Voltage Selection Operating Instructions Normal Mode OperationBypass Mode Operation Battery Recharge Mode Battery Mode OperationCommunications Pins 4 & 5 Remote Shutdown on BatteryCommunications Interface Port Pin Assignment DescriptionAuto-Enable Output Pin 6 Logic Pins 5 & 6 Any-Mode ShutdownUPS Intelligent Communications Liebert GXT2U Configuration Program Abilities Configuration ProgramBattery Replacement MaintenanceInternal Battery Replacement Procedures On bypass due to overtemperature condition beep every 4 sec TroubleshootingOn bypass due to DC bus overvoltage beep every 4 sec On bypass due to PFC failure beep every 4 secProblem Cause Solution Troubleshooting GuideBattery test is performed Condition Alarm Alarm ConditionsSpecifications WEIGHT, lb kg Battery Cabinet SpecificationsDimensions in mm Internal Battery Battery Run TimesLoad % MinutesProduct Warranty Registration DIS DIS DIS Product Locations Technical Support / ServiceEmerson Network Power