Emerson GXT2U user manual Specifications

Page 33

 

SPECIFICATIONS

 

 

Model Number

GXT2-2700RT208

Model Rating

2700VA/1890W

DIMENSIONS: in. (mm)

 

Unit - W x D x H: in. (mm)

3.5 x 24.2 x 17 (87 x 618 x 430)

Shipping - W x D x H: in. (mm)

10.5 x 27.2 x 23 (268 x 692 x 585)

WEIGHT lbs (kg)

 

Unit: lbs (kg)

75.2 (34.1)

Shipping: lbs (kg)

84.9 (38.5)

INPUT AC PARAMETERS

 

Voltage Range (typical)

208 VAC nominal; variable based on output load

100% - 90% loading

176 VAC/280 VAC

90% - 70% loading

159 VAC/280 VAC

70% - 30% loading

139 VAC/280 VAC

30% - 0% loading

119 VAC/280 VAC

Frequency

40 - 70 Hz; Auto Sensing

Input Power Cord

10 ft. attached w/ NEMA L6-20 plug

OUTPUT AC PARAMETERS

 

Output Receptacles

(2) NEMA L6-15R

(1) NEMA L6-20R

Voltage

200/208/220/230/240 (user configurable) VAC; ±3%

Frequency

50 Hz or 60 Hz

Waveform

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to

 

bypass

BATTERY PARAMETERS

 

Type

Valve-regulated, nonspillable, lead acid

Qty x V x Rating

6 x 12V x 9.0 AH

Battery Mfg/Part #

Panasonic/ UP-VW1245P1

Yuasa/ REW 45-12

Back-Up Time

See Battery Run Times charts

Recharge Time

5 Hours to 95% capacity after full discharge into 100% load

(Internal Batteries Only)

ENVIRONMENTAL

 

Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

Audible Noise

<55 dBA, at 1 meter from the rear

 

<50 dBA, at 1 meter from the front or sides

AGENCY

 

Safety

UL 1778, c-UL Listed

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEEE 587 Category A & B

Transportation

ISTA Procedure 1A

29

DISCONTINUED

PRODUCT

 

Image 33
Contents Liebert GXT2U DIS Product Table of Contents Operating Instructions Important Safety Instructions DIS Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitMajor Components Transient Voltage Surge Suppression and EMI/RFI FiltersBattery DC-to-DC ConverterDynamic Bypass Liebert GXT2U-Rear View Tower UPS Installation InstallationPreparation Base to accommodateOptional rack mount handles Rack-Mount UPS Conversion and InstallationM5 screws Mounting railsApply grease UPS or battery cabinet Apply grease inside External Battery Cabinet Installation DIS ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsFault Indicator LED Red Load/Battery Level Indicators 4 Green, 1 AmberBypass Indicator LED Amber UPS on Indicator LED GreenOutput Voltage Selection Normal Mode Operation Bypass Mode OperationOperating Instructions Battery Recharge Mode Battery Mode OperationCommunications Pins 4 & 5 Remote Shutdown on BatteryCommunications Interface Port Pin Assignment DescriptionAuto-Enable Output Pin 6 Logic Pins 5 & 6 Any-Mode ShutdownUPS Intelligent Communications Liebert GXT2U Configuration Program Abilities Configuration ProgramBattery Replacement MaintenanceInternal Battery Replacement Procedures On bypass due to overtemperature condition beep every 4 sec TroubleshootingOn bypass due to DC bus overvoltage beep every 4 sec On bypass due to PFC failure beep every 4 secProblem Cause Solution Troubleshooting GuideBattery test is performed Condition Alarm Alarm ConditionsSpecifications Battery Cabinet Specifications Dimensions in mmWEIGHT, lb kg Internal Battery Battery Run TimesLoad % MinutesProduct Warranty Registration DIS DIS DIS Product Technical Support / Service Emerson Network PowerLocations
Related manuals