Emerson GXT2U user manual Internal Battery Replacement Procedures

Page 28

Internal Battery Replacement Procedures

1.Gently remove the front plastic bezel cover from the UPS.

2.Loosen and remove the four screws on the front battery door. Lay the bat- tery door aside for reassembly.

3.Gently pull battery wiring out and disconnect the two slotted battery con- nectors.

4.Grasp the battery pack assembly, and pull it out of the front of the UPS.

5.Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 6; otherwise STOP and contact your local dealer, Lie- bert representative, or the Liebert Worldwide Support Group.

6.Line up and slide in the new replacement battery pack.

7.Reconnect the two slotted battery connectors and gently push the battery wiring and battery pack assembly back into the UPS.

8.Reattach the front battery door with the four screws.

9.Reattach the front plastic bezel cover to the UPS.

NOTE

These are hot-swappable replacement batteries. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.

24

DISCONTINUED

PRODUCT

 

Image 28
Contents Liebert GXT2U DIS Product Table of Contents Operating Instructions Important Safety Instructions DIS Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerMajor Components Transient Voltage Surge Suppression and EMI/RFI FiltersDC-to-DC Converter BatteryDynamic Bypass Liebert GXT2U-Rear View Installation Tower UPS InstallationPreparation Base to accommodateRack-Mount UPS Conversion and Installation Optional rack mount handlesMounting rails M5 screwsApply grease UPS or battery cabinet Apply grease inside External Battery Cabinet Installation DIS Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonLoad/Battery Level Indicators 4 Green, 1 Amber Fault Indicator LED RedBypass Indicator LED Amber UPS on Indicator LED GreenOutput Voltage Selection Bypass Mode Operation Normal Mode OperationOperating Instructions Battery Mode Operation Battery Recharge ModePins 4 & 5 Remote Shutdown on Battery CommunicationsCommunications Interface Port Pin Assignment DescriptionPins 5 & 6 Any-Mode Shutdown Auto-Enable Output Pin 6 Logic UPS Intelligent Communications Configuration Program Liebert GXT2U Configuration Program AbilitiesMaintenance Battery ReplacementInternal Battery Replacement Procedures Troubleshooting On bypass due to overtemperature condition beep every 4 secOn bypass due to DC bus overvoltage beep every 4 sec On bypass due to PFC failure beep every 4 secTroubleshooting Guide Problem Cause SolutionBattery test is performed Alarm Conditions Condition AlarmSpecifications Dimensions in mm Battery Cabinet SpecificationsWEIGHT, lb kg Battery Run Times Internal BatteryLoad % MinutesProduct Warranty Registration DIS DIS DIS Product Emerson Network Power Technical Support / ServiceLocations