Emerson 240V, 208 user manual Change Configuration Settings Change Settings Menu

Page 27

Operating Instructions

Change Configuration Settings - Change Settings Menu

Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration screen, select the Change Settings option. You may configure Nfinity from a large variety of selec- tions. Items indicated by an asterisk (*) are the selected settings.

Main Menu

UPS Status

>UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools

UPS Configuration

UPS Configuration

Review Settings

>Change Settings Service Mode

Change Settings

Input Voltage

Display Voltage

Frequency Sync Range

Frequency Slew Rate

Set Password

Auto Battery Test

Low Battery Warning

Auto Restart

User Settings

Set Date/Time

Max Load Alarm Set

UPS Shutdown Delay

Redund Alarm Set

Service Contact

Remote Shutdown

External Battery

Bypass Alarm Mode

Intelli-Batt Ca.

Air Filter Reminder

Guarantee Shutdown

Line Compensation

Factory Defaults

Input Voltage: Select the required input voltage set- ting. This voltage must match the bypass voltage jumper setting.

Input Voltage

*208/120

240/120

Display Voltage: Displays the actual voltage the unit is configured for.

Display Voltage 208

* 240

Frequency Sync Range: Sets the window to which the system synchronizes to the input supply.

Frequency Sync Range

0.5Hz

1.0Hz

2.0Hz

3.0Hz

4.0Hz

*5.0 Hz

Frequency Slew Rate: Sets the rate of change of frequency through the sync range window.

Frequency Slew Rate

0.5Hz

1.0Hz

2.0Hz

3.0Hz

4.0Hz

*5.0 Hz

Set Password: Set a Password to prevent unautho- rized users from changing the configuration of the Nfinity. It can be up to seven characters in length. Once set, the password will be required to change the configuration.

Set Password xxxxxxx

NOTE

If the password is lost, call Liebert Technical Support.

23

Image 27
Contents Nfinity Power System Page Table of Contents Figures Important Safety Instructions Glossary of Symbols Standard Components FeaturesGeneral Description System DescriptionFront and back views Nfinity weight and dimensionsBypass Mode Normal ModeBackup Mode Auto Restart ModeSystem Control Module Major ComponentsUnit Frame User Interface ModuleBattery Module Power ModuleSite Preparation Required Setup EquipmentInspection EnvironmentUnloading the UPS UnloadingStationary Mounting Cable Installation Wiring PreparationConfiguring the Bypass Voltage TB2 Input Wiring TB1 Output Wiring TB3Grounding Conductor Installation Bypass Voltage Jumper Position TB2 Connecting to External Panel Boards208 VAC Setup 1 208 VACSetup 2 120 VAC Setup 3 240 VACRepo Connection Repo switch connectionsCOM2 Serial CommunicationsCOM Ports COM1 Relay ContactsButtons Controls and IndicatorsFault/Warning and Status LEDs Display ControlsNavigating the Menu Status LED ModesShutting Down the UPS Operating ProceduresStart-Up and Initialization Manual Transfer to BypassDisplay Date/Time UPS Status Event Log Module ReplacementUPS Configuration Active Alarms Service Tools Main MenuUPS Status Screen UPS Configuration Screen Review Settings Change Settings Change Configuration Settings Change Settings MenuStart Day Auto Restart ModeAuto Restart Delay IntervalThreshold DST ModeAlarm Mode Set Date/TimeGuarantee Shutdown Enable UPS Configuration Screen Service Mode Menu Service ModeDisplay Date/Time Active Alarms Event LogTransfer to Bypass Module Replacement Clear Failures Service Tools for Liebert Global Services EngineersUser Interface Text Cause Action Active AlarmsOperation Control Module Power ModuleBattery Module Guide to LEDs Module LED IndicationRemoving Modules Module ReplacementReplacing the User Interface Adding or Replacing ModulesReplacing Fan Filters MaintenanceScheduled Maintenance Proper CareSpecifications Product Warranty RegistrationSpecifications Page Technical Support/Service Company Behind the ProductsLocations