Emerson 240V, 208 DST Mode, Set Date/Time, Alarm Mode, Threshold, Company Name, Phone Number

Page 29

Operating Instructions

Set Date/Time: Allows user to enable/disable DST (Daylight Saving Time), change the Day, Date and Time setting on Nfinity. When enabled, the time will automatically adjust to Daylight Saving Time.

Set Time/Date

DST Mode

Set Time/Date

DST Mode

DST Mode

Enabled

* Disabled

Set Date/Time

Date/Time

MM/DD/YYYY HH:MM:SS

Max Load Alarm Set: Allows an alarm to set when Nfinity’s load reaches a specific level.

Max Load Alarm Set

Mode

Threshold

Alarm Mode

Max Load Alarm Mode

*Enable Disable

Threshold

Max Load Alarm Set

Threshold kVA = xx.x

UPS Shutdown Delay: Delays UPS shutdown for specified amount of time after receiving shutdown command via relay contacts only.

UPS Shutdown Delay xxx seconds

Redundant Alarm Set: Sets Alarm to notify user when redundancy is no longer available.

Redundant PWR Alarm Set

Enable

* Disable

Service Contact: Set a contact for the user to reach if problems occur.

Service Contact

>Company Name

Company Phone

Company Name

Company/Name

LIEBERT CORP.

Phone Number

Phone Number

WWW.LIEBERT.COM

Remote Shutdown: Enables / Disables the Remote Communications Shutdown.

If you are using MultiLink™ software, this parameter should be enabled in order for the UPS output to be turned off once the operating system has been shut- down.

Remote Shutdn

*Enable Disable

External Battery: Sets total amp-hour for external batteries to provide a more accurate runtime remain- ing value on the LCD display and through communi- cations.

External Battery

Amp-hour

> Charge Current

External Batt Config Enter total amp-hour

0000

External Batt Config Enter charge current

00.0

When using the Non-Modular External Battery Cabinets with Chargers (P/N: PB10SLF105WC120), enter the following:

# Cabinets

AH Value

Charge Current

1

0091

07.0

2

0182

14.0

3

0273

21.0

4

0364

28.0

5

0455

35.0

6

0546

42.0

25

Image 29
Contents Nfinity Power System Page Table of Contents Figures Important Safety Instructions Glossary of Symbols General Description FeaturesSystem Description Standard ComponentsFront and back views Nfinity weight and dimensionsBackup Mode Normal ModeAuto Restart Mode Bypass ModeUnit Frame Major ComponentsUser Interface Module System Control ModuleBattery Module Power ModuleInspection Required Setup EquipmentEnvironment Site PreparationUnloading the UPS UnloadingStationary Mounting Configuring the Bypass Voltage TB2 Cable InstallationWiring Preparation Grounding Conductor Installation Input Wiring TB1Output Wiring TB3 Bypass Voltage Jumper Position TB2 Connecting to External Panel BoardsSetup 2 120 VAC Setup 1 208 VACSetup 3 240 VAC 208 VACRepo Connection Repo switch connectionsCOM Ports CommunicationsCOM1 Relay Contacts COM2 SerialFault/Warning and Status LEDs Controls and IndicatorsDisplay Controls ButtonsNavigating the Menu Status LED ModesStart-Up and Initialization Operating ProceduresManual Transfer to Bypass Shutting Down the UPSUPS Configuration Active Alarms Service Tools UPS Status Event Log Module ReplacementMain Menu Display Date/TimeUPS Status Screen UPS Configuration Screen Review Settings Change Settings Change Configuration Settings Change Settings MenuAuto Restart Delay Auto Restart ModeInterval Start DayAlarm Mode DST ModeSet Date/Time ThresholdGuarantee Shutdown Enable Display Date/Time UPS Configuration Screen Service Mode MenuService Mode Transfer to Bypass Active AlarmsEvent Log Module Replacement Clear Failures Service Tools for Liebert Global Services EngineersUser Interface Text Cause Action Active AlarmsOperation Battery Module Guide to LEDs Power ModuleModule LED Indication Control ModuleRemoving Modules Module ReplacementReplacing the User Interface Adding or Replacing ModulesScheduled Maintenance MaintenanceProper Care Replacing Fan FiltersSpecifications Product Warranty RegistrationSpecifications Page Locations Technical Support/ServiceCompany Behind the Products