Operating Instructions

3.5.7Module Replacement

The user interface also supplies instructions for removing and replacing modules. From the Main Menu, access the module replacement screen and select the type of module. Refer to the screens below:

Main Menu

UPS Status

UPS Configuration

Display Date/Time

Event Log

Active Alarms

Transfer to Bypass

>Module Replacement Service Tools

Module Replacement

Module Replacement

>Ctrl w/ Redundant Ctrl w/o Redundant Pwr w/ Redundant Pwr w/o Redundant Battery Module

Module Replacement menu options

Control Module w/ Redundant

Cntl Mod Replacement

1.Lift off display panel and place on top of UPS

2.Locate amber LED

3.Open lever

4.Loosen fastener

5.Replace module

6.Tighten fastener

7.Close lever

8.Replace display

Control Module w/o Redundant

Cntl Mod Replacement

1.Remove bottom bezel and place UPS in bypass

2.Lift off display panel and place on top of UPS

3.Locate amber LED

4.Open lever

5.Loosen fastener

6.Replace module

7.Tighten fastener

8.Close lever

9.Wait for amber LED to stop flashing.

10.Replace display 11.Switch bypass to return to UPS

operation 12.Replace bezel

Power Module w/ Redundant

Pwr Mod Replacement

1.Remove all front bezels

2.Locate amber LED

3.Open lever

4.Loosen fastener

5.Replace module

6.Tighten fastener

7.Close lever

8.Replace all bezels

Power Module w/o Redundant

Pwr Mod Replacement

1.Remove bottom bezel and place UPS in bypass

2.Remove remaining front bezels

3.Locate amber LED

4.Open lever

5.Loosen fastener

6.Replace module

7.Tighten fastener

8.Close lever

9.Wait for amber LED

to stop flashing. 10.Switch bypass to

return to UPS operation

11.Replace all bezels

Battery Module

Battery Module

1.Remove all front bezels

2.Locate amber LED

3.Loosen fastener

4.Replace module

5.Tighten fastener

6.Replace all bezels

For more details on module replacement, consult 4.0 - Troubleshooting.

29

Image 33
Contents Nfinity Power System Page Table of Contents Figures Important Safety Instructions Glossary of Symbols General Description FeaturesSystem Description Standard ComponentsFront and back views Nfinity weight and dimensionsBackup Mode Normal ModeAuto Restart Mode Bypass ModeUnit Frame Major ComponentsUser Interface Module System Control ModuleBattery Module Power ModuleInspection Required Setup EquipmentEnvironment Site PreparationUnloading the UPS UnloadingStationary Mounting Cable Installation Wiring PreparationConfiguring the Bypass Voltage TB2 Input Wiring TB1 Output Wiring TB3Grounding Conductor Installation Bypass Voltage Jumper Position TB2 Connecting to External Panel BoardsSetup 2 120 VAC Setup 1 208 VACSetup 3 240 VAC 208 VACRepo Connection Repo switch connectionsCOM Ports CommunicationsCOM1 Relay Contacts COM2 SerialFault/Warning and Status LEDs Controls and IndicatorsDisplay Controls ButtonsNavigating the Menu Status LED ModesStart-Up and Initialization Operating ProceduresManual Transfer to Bypass Shutting Down the UPSUPS Configuration Active Alarms Service Tools UPS Status Event Log Module ReplacementMain Menu Display Date/TimeUPS Status Screen UPS Configuration Screen Review Settings Change Settings Change Configuration Settings Change Settings MenuAuto Restart Delay Auto Restart ModeInterval Start DayAlarm Mode DST ModeSet Date/Time ThresholdGuarantee Shutdown Enable UPS Configuration Screen Service Mode Menu Service ModeDisplay Date/Time Active Alarms Event LogTransfer to Bypass Module Replacement Clear Failures Service Tools for Liebert Global Services EngineersUser Interface Text Cause Action Active AlarmsOperation Battery Module Guide to LEDs Power ModuleModule LED Indication Control ModuleRemoving Modules Module ReplacementReplacing the User Interface Adding or Replacing ModulesScheduled Maintenance MaintenanceProper Care Replacing Fan FiltersSpecifications Product Warranty RegistrationSpecifications Page Technical Support/Service Company Behind the ProductsLocations