Specifications
6.0SPECIFICATIONS
General & Environmental | Units |
|
| Configuration |
|
|
| |||
Unit Rating |
| kVA | 12 |
| 16 |
| 20 |
| 20 | |
| kW | 8.4 |
| 11.2 |
| 14 |
| 16 | ||
|
|
|
|
|
| |||||
Conducted and Radiated EMC Levels |
|
|
| FCC Part 15, Class A |
|
|
| |||
Compliant Safety Standards |
|
|
| UL 1778; |
|
|
| |||
Compliant Immunity Standards |
|
| IEEE C62.41, Category B |
|
|
| ||||
Mechanical |
| Units |
|
|
|
|
|
|
| |
|
| Width |
|
|
| 20 (508) |
|
|
| |
Dimensions |
| Depth | in (mm) |
|
| 28 (711) |
|
|
| |
|
| Height |
|
|
| 54 (1372) |
|
|
| |
Environmental |
|
| Units |
|
|
|
|
|
|
|
Operating Temperature (max) | C (F) |
|
| 0° - 40° (32° - 104°) |
|
| ||||
Relative Humidity |
| % |
|
|
|
| ||||
Maximum operating altitude | M (ft.) |
|
| 3,000 (10,000) |
|
|
| |||
Nominal heat dissipation |
| BTU/Hr | 3,186 |
| 4,248 |
| 5,903 |
| 6,748 | |
Acoustic noise level |
| dBA |
|
| <62 @ | 1 meter |
|
|
| |
Input Data |
| Units |
|
|
|
|
|
|
| |
Nominal input voltage |
| VAC |
|
| 208 or 240 |
|
|
| ||
|
|
|
| 208VAC nominal: operating voltage range variable based on output loading percentages | ||||||
|
|
|
| % UPS Load |
|
|
| Input Voltage | ||
Voltage Range (Typical) |
|
| 80 – 100% |
|
|
| 170 VAC | |||
|
| 60 – 80% |
|
|
| 144 VAC | ||||
|
|
|
|
|
|
| ||||
|
|
|
| 30 – 60% |
|
|
| 127 VAC | ||
|
|
|
| 0 – 30% |
|
|
| 110 VAC | ||
Power factor |
| Cos ∅ |
|
| >.98 |
|
|
| ||
Input frequency (nominal) | Hz |
|
| 60 |
|
|
| |||
Input frequency range |
| Hz |
|
|
|
|
| |||
Battery Module |
| Units |
|
|
|
|
|
|
| |
Number of lead acid batteries |
|
|
| 10 |
|
|
| |||
Number of battery cells |
|
|
|
| 60 |
|
|
| ||
Battery capacity |
| A/hr |
|
| 9 |
|
|
| ||
Autonomy time (full load) | minutes | 6 (With an equal number of Battery & Power Modules, in a | ||||||||
Maximum charge current (full load) | A |
|
| 3 |
|
|
| |||
Nominal Voltage |
| VDC |
|
| 120 |
|
|
| ||
Recharge Time |
| Hrs |
|
| Typically 6 (to 90% capacity) |
|
| |||
Output Data |
| Units |
|
|
|
|
|
|
| |
Output voltage |
| VAC |
|
| 208/120 or 240/120 |
|
| |||
Voltage regulation |
| % |
|
| ±3 |
|
|
| ||
Voltage stability (100% step load) | % |
|
| ±7 |
|
|
| |||
Recovery time |
| msec |
|
| 96 |
|
|
| ||
Voltage distortion |
| % |
|
| <3 THD, linear load |
|
| |||
|
|
| <7 THD, |
|
| |||||
|
|
|
|
|
|
|
| |||
Output frequency |
| Hz |
|
| 60 |
|
|
| ||
Efficiency at 100% load |
| % |
|
| 89 |
|
|
| ||
|
|
|
|
|
| 110 - 125% for 10 min |
|
| ||
Output overload capability | % |
|
|
|
| |||||
|
|
|
|
|
| 151 - 200% for 2 cycles |
|
|
6.1Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at: http://www.liebert.com
•Click on Product Warranty Registration and fill in the form. If you have any questions, please contact us at:
US:
Outside the US:
upstech@liebert.com
37