TRENDnet SMT1000 operation manual Low Transfer Point

Page 11

Function

Factory Default

Options

Description

 

 

 

 

 

 

 

100 Vac:

86 Vac - 92 Vac

Set the transfer point lower if the utility voltage is

 

 

92 Vac

chronically low and the connected equipment can

 

 

 

 

 

 

 

tolerate this condition.This setting may also be adjusted

Low Transfer Point

120 Vac:

97 Vac - 106 Vac

using the power quality setting.

106 Vac

 

 

 

 

 

 

 

 

Note: Use the Advanced Menus to configure this

 

 

230 Vac:

196 Vac -208 Vac

 

 

208 Vac

setting.

 

 

 

 

 

 

 

 

 

 

100 Vac

N/A

 

 

 

 

 

 

Nominal Output

120 Vac

N/A

230 Vac models only: Set the nominal output voltage of

 

 

Voltage

 

 

• 220 Vac

the UPS to standby mode.

 

 

230 Vac

• 230 Vac

 

 

 

 

• 240 Vac

 

 

 

 

 

 

 

 

 

 

Select the level of sensitivity to power events that the

 

 

 

 

UPS will tolerate.

 

 

 

 

Normal: The UPS will go on battery power more

 

 

 

 

often to provide the cleanest power supply to the

Transfer Sensitivity

Normal

Normal, Reduced, Low

connected equipment.

Low: The UPS will tolerate more fluctuations in

 

 

 

 

power and will go on battery power less often.

 

 

 

 

If the connected load is sensitive to power disturbances,

 

 

 

 

set the sensitivity to Normal.

 

 

 

 

Low Battery Warning

120 sec

Set the value in seconds

The UPS will emit an audible alarm when the remaining

 

 

 

 

runtime has reached this level.

 

 

 

 

 

Date of Last Battery

Date set at factory

Reset this date when the battery module is replaced.

Replacement

 

 

 

 

 

 

 

 

Audible Alarm

On

On/Off

The UPS will mute all audible alarms if this is set to Off

or when the display keys are pressed.

 

 

 

 

 

 

 

 

 

Battery

On start up and every

• Never

The interval at which the UPS will execute a

• Start up only

Self-Test Interval

14 days since the last

• Frequency of test

self-test.

Setting

test

(every 7 to 14 days)

 

 

 

 

 

 

 

 

 

Reset to Factory

No

Yes/No

Restore the UPS factory default settings.

Default

 

 

 

 

 

 

 

 

Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower

9

Image 11
Contents Smart-UPSUninterruptible Power Supply Page Product Description Important Safety MessagesSafety and General Information OverviewEnvironmental SpecificationsProduct Overview Front panel featuresRear panel features 500 VA to 1500 VA models 2200/3000 VA 100 Vac 2200/3000 VA 230 Vac 3000 VA 120 Vac InstallationRear panel features 2200 VA and 3000 VA models 2200 VA 120 VacConnect Equipment Rear Panel FeaturesOperation Menu General Functions Using the display interfaceDisplay Panel Standard menusLog Advanced menusControl General Settings ConfigurationUPS Settings Start up SettingsLow Transfer Point Overview Using the Main and Controlled Outlet GroupsMain Outlet Group and Controlled Outlet Group Customize the Main and Controlled Outlet Groups Network Management Card SettingsNormally closed contacts Emergency Power OffNormally open contacts UPS is emits intermittent beeps TroubleshootingUPS does not provide expected backup time UPS displays a site wiring fault messageTransport the unit ServiceTwo Year Limited Factory Warranty EN 990-3534D 03/2013 APC by Schneider Electric Worldwide Customer Support