Customize the Main and Controlled Outlet Groups
Use the Configuration menus to change the Main Outlet Group and the Controlled Outlet Group settings.
Function | Factory Default | Options | Description | |
|
|
|
| |
Name String | Outlet Group 1 | Edit these names using an external interface, such as the Network | ||
Outlet Group | ||||
| ||||
|
| Management Card Web interface. | ||
UPS Name String | UPS Outlets | |||
|
| |||
|
|
|
| |
Turn On Delay |
| Set the value in | The amount of time the UPS or a Controlled Outlet | |
0 sec | Group will wait between receiving the command to | |||
seconds | ||||
|
| turn on and the actual startup. | ||
|
|
| ||
|
|
|
| |
Turn Off Delay | • 0 sec UPS Outlets | Set the value in | The amount of time the UPS or a Controlled Outlet | |
• 90 sec Controlled | Group will wait between receiving the command to | |||
seconds | ||||
| Outlet Groups | turn off and the actual shut down. | ||
|
| |||
|
|
|
| |
Reboot Duration | 8 sec | Set the value in | The amount of time the UPS or a Controlled Outlet | |
seconds | Group must remain off before it will restart. | |||
|
| |||
|
|
|
| |
Minimum Return |
| Set the value in | The amount of battery runtime that must be available | |
0 sec | before the UPS or a Controlled Outlet Group will | |||
Time | seconds | |||
| turn on after a shutdown. | |||
|
|
| ||
|
|
|
| |
|
| • Enable | When the unit switches to battery power, the UPS | |
|
| • Disable | will disconnect power to the Controlled Outlet | |
Load Shed On |
|
| Group to save battery runtime. | |
Disabled |
|
| ||
Battery |
| Configure this delay time, use the LOAD SHED TIME | ||
|
| |||
|
|
| WHEN ON BATTERY setting. | |
|
|
|
| |
Load Shed Time | 1800 sec | Set the value in | The amount of time the outlets will function on | |
when On Battery | seconds | battery power before they will turn off. | ||
| ||||
|
|
|
| |
|
| • Enable | When the battery runtime falls below the specified | |
Load Shed On | Disabled | • Disable | value, the Controlled Outlet Group will turn off. | |
|
| |||
Runtime |
| Configure this time using the LOAD SHED RUNTIME | ||
|
| |||
|
|
| ||
|
|
| REMAINING setting. | |
|
|
|
| |
Load Shed On |
| Set the value in | When the remaining runtime reaches this level, the | |
Runtime | 120 sec | |||
seconds | Controlled Outlet Group will turn off. | |||
Remaining |
| |||
|
|
| ||
|
|
|
| |
|
| • Disabled | In the event of an overload (greater than 107% | |
Load Shed on | Disabled | • Enabled | output), the Controlled Outlet Group will | |
| immediately turn off to conserve power for critical | |||
Overload |
| |||
|
| loads. The Controlled Outlet Group will only turn on | ||
|
|
| ||
|
|
| again with a manual command. | |
|
|
|
|
Network Management Card Settings