TRENDnet SMT1000 operation manual Main Outlet Group and Controlled Outlet Group, Overview

Page 12

Main Outlet Group and Controlled Outlet Group

Overview

The Main Outlet Group and the Controlled Outlet Group can be configured to independently turn off,

turn on, shut down, and reboot connected equipment. (These features are not available on the 500 VA or 750 VA units.)

The Main and Controlled Outlet Groups can be configured to do the following:

Turn off: Disconnect from power immediately and restart only with a manual command.

Turn on: Connect to power immediately.

Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power becomes available.

Reboot: Shut down and restart.

In addition, the Main Outlet Group and the Controlled Outlet Group can be configured to do the following:

Turn on or off in a specified sequence

Automatically turn off or shut down when various conditions occur

Note: If the Main and Controlled Outlet Groups are not configured, all of the outlets on the unit will still provide battery backup power.

Using the Main and Controlled Outlet Groups

The Main Outlet Group functions as a master switch. It will turn on first when power is applied, and shut down last when there is a power outage and battery runtime has been exhausted.

The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.

1.Connect critical equipment to the Main Outlet Group.

2.Connect peripheral equipment to the Controlled Outlet Group.

Nonessential equipment that should shut down quickly in the event of a power outage can be added to a short power off delay, to conserve battery runtime.

Equipment that has dependent peripherals that must restart or shut down in a specific order should be connected to a separate outlet group.

Equipment that needs to reboot independently from other equipment should be added to a separate outlet group.

3.Use the Configuration menus to set reaction of the Controlled Outlet Group in the event of a power outage.

10

Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower

Image 12
Contents Smart-UPSUninterruptible Power Supply Page Important Safety Messages Safety and General InformationOverview Product DescriptionSpecifications EnvironmentalFront panel features Rear panel features 500 VA to 1500 VA modelsProduct Overview Installation Rear panel features 2200 VA and 3000 VA models2200 VA 120 Vac 2200/3000 VA 100 Vac 2200/3000 VA 230 Vac 3000 VA 120 VacRear Panel Features OperationConnect Equipment Using the display interface Display PanelStandard menus Menu General FunctionsAdvanced menus ControlLog Configuration UPS SettingsStart up Settings General SettingsLow Transfer Point Using the Main and Controlled Outlet Groups Main Outlet Group and Controlled Outlet GroupOverview Network Management Card Settings Customize the Main and Controlled Outlet GroupsEmergency Power Off Normally open contactsNormally closed contacts Troubleshooting UPS does not provide expected backup timeUPS displays a site wiring fault message UPS is emits intermittent beepsService Transport the unitTwo Year Limited Factory Warranty APC by Schneider Electric Worldwide Customer Support EN 990-3534D 03/2013