UPS configurations
1.Various settings that have been chosen are shown in the UPS setting display.
2.To enter configuration mode, press the “FUNC” button for one second. The first configuration parameter will be shown on the LCD display.
3.Press the “FUNC” button to scroll through the parameters.
4.Press the “ENTER” button to select the parameter.
5.Press the “FUNC” button to scroll through the options for the selected parameter.
6.Press the “ENTER” button to select the option.
You may be prompted to save the selection, if so press the “ENTER” button to either confirm or save your selection. Other options are saved and started automatically. See the table below for further details.
7.If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the configuration mode and return to normal mode displaying Line mode.
Caution!
The factory default settings do not necessarily have to be changed, although you are free to tailor the UPS to your specific needs.
22
Settings | LCD | Explanation | Selection | Factory | |
display | default | ||||
|
|
| |||
|
|
|
|
| |
Output Volt.Setting | O/P V | Select Nominal Voltage | 208/220/230/240 V | 230V | |
Setting | |||||
|
|
|
|
| |
|
| Select input frequency | ±2% |
| |
Input/Frequency | I/P F Setting | range when UPS goes into | ±5% | ±5% | |
|
| free run mode | ±7% |
| |
Input/Bypass | I/P Bypass | Select Input Voltage range | ±10% |
| |
Voltage | Set | when bypass is available | |||
| |||||
|
|
|
| ||
| Free Run | Select if UPS can run in |
|
| |
Free Run Mode | Free run mode | ON/OFF | ON | ||
Set | |||||
| (unsynchronized) |
|
| ||
|
|
|
| ||
Bypass | Bypass | If Enable is chosen, the |
|
| |
Enable/Disable at | UPS can go to bypass when | Disable/Enable | Disable | ||
disable | |||||
Free run mode | unsynchronized. |
|
| ||
|
|
| |||
|
|
|
|
| |
He mode Setting | HE Mode | Select if UPS runs in high | ON/OFF | OFF | |
Set | efficiency mode | ||||
|
|
| |||
Force Manual | Manual | Permanently force UPS to | ON/OFF | OFF | |
Bypass | bypass | bypass. For service only.** | |||
|
|
|
|
| |
Do Battery Test | Battery Test | Detect battery is normal or |
|
| |
|
| not. |
|
| |
Silence Function | Silence Set | Enable or disable silence | ON/OFF | OFF | |
function | |||||
|
|
|
| ||
|
|
|
|
| |
Number of | Bat Cabinet | This setting is needed | 0 (only internal batteries) | 0 | |
External battery | Set | For UPS to predict | 1(one external cabinet) | ||
Packs | Backup time | 2 (two external cabinets) |
| ||
|
| ||||
|
|
|
|
| |
Site wiring alarm | Sit Fault Set | You can enable or disable | Enable /Disable | Disable | |
|
| the site wiring alarm |
|
| |
Select Language | Language | Select load language | English, German, French, | English | |
|
|
| Spanish, Italian. |
| |
Set Generator Mode | Generator | Set unit in generator mode. | ON/OFF | OFF | |
|
| *** |
|
| |
Set RS232 | RS232 | Set RS232 communication | Enable/Disable | Enable | |
communication | Control | enable or disable | |||
|
| ||||
|
|
|
|
|
Manual test of the UPS
Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well and are functional even when the UPS is not charging the battery.
Manual Battery test: Scroll the parameters until Manual Bat test displays on the LCD. Press the “ENTER” button twice.