3. Safety information

Information presented here is vital to all personnel and please also read the UPS safety manual.

Storage and Transportation

Please handle with extreme caution since a high amount of energy is contained with the batteries. Always keep the unit in position as marked on the packaging and never drop the unit.

Installation

If flammable substances such as gases or fumes are present or if the room is airtight, a safety hazard situation exists, in which no electrical equipment should be operated.

The instructions in this manual explain how to install the UPS safely. Not acknowledging such electrical hazards may be fatal, so keep this manual for all future reference.

WARNING!

It is strongly advisable not to open the UPS cabinet as the components have very high voltage and touching them may be fatal. Only a technician from the manufacturer or an authorized agent may service the unit.

This UPS unit’s output receptacles carry live voltage even when not connected to a power supply as it has its own energy source.

User’s operations

The only operations that users are permitted to do are:

zTurning the UPS unit on and off

zOperating the users interface

zConnecting data interface cables

All such operations are to be performed exactly as instructed in this manual. The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator.

4. Storage

Please adhere to the following instructions if the UPS is not installed immediately:

zStore the equipment as is in its original packing and shipping carton

zDo not store in temperatures outside the range of +15°C to +25°C.

zEnsure that the equipment is fully protected from wet or damp areas and from moist air.

In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8 hours.

5. Installation

5.1 Environment

Ensure that all environmental concerns and requirements are met according to these technical specifications, otherwise the safety of installation personnel cannot be guaranteed and the unit may malfunction.

Ensure that you remember the following when locating the UPS system and battery options:

zAvoid extremes of temperature and humidity. Maximal battery life can be attained with a recommended temperature range of 15 °C to 25 °C.

zProvide protection for the equipment from moisture.

zSpace and ventilation requirements must be met. Ensure there is 100mm behind and 50mm on the sides of the UPS for ventilation.

zEnsure that the front of the UPS remains clear for user operation.

The External Battery Cabinets has to be installed next to the UPS or under the UPS.

Caution! The UPS and the External Battery Pack are to be installed at the same location. In case, the UPS and the External Battery Pack are installed outside of visible distance, then subject to the local inspection authority, User will need to add a Safety disconnect adjacent to the UPS to provide safety isolation.

4

5

Image 5
Contents Declaration of Conformity Request 4K VA 20K VA UPS Important Safety Instructions Save These Instruction General description IntroductionSystem description Free Run Mode System configurationDiagnostic tests Efficiency Optimizer functionInstallation Safety informationStorage EnvironmentRear panel views 6KVA Rear panel With ISO 8K~10KVA Rear panel Without ISO 8K~10 KVA 12KVA Rear panel ISO and With ISO Or kill personnel and damage equipment Connection to mains and loads 4000 20000 VAOnly required if demanded by that of local wiring rules Default settings at the factory Computer and alarm connectionsConnecting the UPS to a Computer RS-232 Standard Interface portUser’s guide to operations EPO port emergency power offStarting and shutting down the UPS Button operationNormal display Control panel functionsUPS meters display LCD messageManual test of the UPS UPS configurationsInterpreting UPS messages Alarm indicatorsSilencing an alarm Trouble shooting MaintenanceFor model with 3 Phase in 1 Phase out Technical SpecificationsFor Rack mount model 6K-ISO TB VGD RM 6KVA3U+3U Mechanical Connect the Battery cabinet to UPSPage Tower installation Installation with rear Bracket Wall installation