EMC 4K VA 20K VA UPS installation manual Connection to mains and loads 4000 20000 VA

Page 9

15/20 KVA Rear panel

5.3 Connection to mains and loads (4000 - 20000 VA)

Only qualified specialists or technicians who conform to applicable safety

(ISO and With ISO)

standards may carry out the installation of this equipment. The installation must

 

further comply with all local legislation and regulations.

 

Follow all installation and safety instructions very carefully, otherwise those

 

performing installation may suffer from a hazardous situation and the UPS or

 

load connections may also be damaged.

 

 

The high voltage and current contained within the UPS equipment can injure

 

 

or kill personnel and damage equipment.

 

For electrical installation, closely observe the nominal current rating of the source.

 

Installing External battery cabinets

 

z

First disconnect the UPS from mains and loads before attempting an

 

 

External Battery Cabinet installation.

 

z

Use the battery cable provided with the External Battery Cabinet to

 

 

connect the External Battery Cabinet to the UPS. Connect a second

 

 

battery cabinet to the first one with the cable provided if more than one is

 

 

to be installed.

 

z

Be aware of UPS parameters and changing the Battery pack quantity

 

 

when using the external battery cabinets (see chapter 7.2)

 

Installing UPS

 

z

Ensure that the installation site has all electrical connections properly

 

 

carried out. In addition, refer to figures 2 and 3 to check the fuse and

 

 

cable dimensions.

 

z

Isolate and secure the source against reclosing. Both input and output

 

 

circuit breakers (located in the back) must be “OFF”.

 

z

Refer to figure 2 for single cable input and figure 3 for dual cable input.

 

 

Connect the UPS according to these diagrams. If installing dual cables,

 

 

the interconnection jumper (b*) needs to be removed as in figure 2. Fuse

 

 

and cable sizes are given in figure 3.

 

z

During installation, if it cannot be determined that neutral is grounded or

 

 

the identification of the neutral status of the mains supply is unreliable,

 

 

an additional two pole disconnect device is necessary in the building

 

 

installation.

 

z

At the back of the unit you will find the Emergency Power Off (EPO),

 

 

which when open will immediately shut down the logic circuit output of

 

 

the UPS as in figure 2 and 3. Wiring the EPO signal is optional.

 

z

Caution! Local safety requirements may require a separate external

 

 

Emergency Power Off that opens output circuit breakers, and if so, use

12

 

13

Image 9
Contents Declaration of Conformity Request 4K VA 20K VA UPSImportant Safety Instructions Save These Instruction Introduction System descriptionGeneral description Free Run Mode System configurationDiagnostic tests Efficiency Optimizer functionInstallation Safety informationStorage EnvironmentRear panel views 6KVA Rear panel With ISO 8K~10KVA Rear panel Without ISO 8K~10 KVA 12KVA Rear panel ISO and With ISO Or kill personnel and damage equipment Connection to mains and loads 4000 20000 VAOnly required if demanded by that of local wiring rules Default settings at the factory Computer and alarm connectionsConnecting the UPS to a Computer RS-232 Standard Interface portUser’s guide to operations EPO port emergency power offStarting and shutting down the UPS Button operationNormal display Control panel functionsUPS meters display LCD messageManual test of the UPS UPS configurationsAlarm indicators Silencing an alarmInterpreting UPS messages Trouble shooting MaintenanceFor model with 3 Phase in 1 Phase out Technical SpecificationsFor Rack mount model 6K-ISO TB VGD RM 6KVA3U+3U Mechanical Connect the Battery cabinet to UPSPage Tower installation Installation with rear Bracket Wall installation