Tripp Lite TMU Series owner manual Troubleshooting, Symptom Problems Corrections

Page 12

Troubleshooting

Try these remedies for common UPS System problems before calling for assistance. Call Tripp Lite Customer Service at (773) 869-1234 before returning your unit for service.

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output (All Indicator Lights are OFF)

Unit is not properly connected to utility power

Connect unit to utility power.

 

 

Operating Mode Switch is set to “OFF” and AC

Set Operating Mode Switch to “AUTO/REMOTE”.

 

 

input is present.

 

 

 

Operating Mode Switch is inadvertently set to

Set Operating Mode Switch to “AUTO/REMOTE”

 

 

“CHARGE ONLY” and AC input is absent.

 

 

 

Circuit breaker is tripped.

Reset circuit breaker.

 

 

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

 

 

battery damage). The problem may be with connected

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE”. If

 

 

auxiliary chargers, if any, or with the unit’s charger.

unit remains in shutdown mode after several attempts to reset,

 

 

 

contact Tripp Lite Customer Service for assistance.

 

 

Unit has shut down due to excessive battery discharge.

Use an auxiliary charger* to raise battery voltage. Check external

 

 

 

battery connections and fuse. Unit automatically resets when

 

 

 

condition is cleared.

 

 

Connected batteries are dead.

Check and replace old batteries.

 

 

Unit has shut down due to overload.

Reduce load. Reset by moving Operating Mode Switch to “OFF”.

 

 

 

Wait 1 minute. Switch to “AUTO/REMOTE”.

 

Battery Not Recharging (AC Input Present)

Connected batteries are dead.

Check and replace old batteries.

 

 

Battery fuse* is blown.

Check and replace fuse.*

 

 

Battery cabling* is loose.

Check and tighten or replace cabling.*

 

 

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

 

 

battery damage). The problem may be with connected

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE”. If

 

 

auxiliary chargers, if any, or with the unit’s charger.

unit remains in shutdown mode after several attempts to reset,

 

 

 

contact Tripp Lite Customer Service for assistance.

 

 

Charger Enable/Inhibit Switch inadvertently set to “INHIBIT.”

Set Charger Enable/Inhibit Switch to “ENABLE”

 

 

Input circuit breaker is tripped.

Reset circuit breaker.

 

All Three “BATT VOLT/CHRG CURR” LEDs

Battery is excessively discharged. Unit will shut down to

Use an auxiliary charger* to raise battery voltage. Check external

are slowly flashing (½ second flashes) with

prevent battery damage.

battery connections and fuse. Unit automatically resets when

Operating Mode Switch in the

 

condition is cleared.

“AUTO/REMOTE” position.

 

 

All Three “BATT VOLT/CHRG CURR” LEDs

Battery is overcharged. Unit will shut down to prevent battery

Disconnect any auxiliary chargers. Reset by moving Operating Mode

are rapidly flashing (¼ second flashes)

damage. The problem may be with connected auxiliary

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE.” If

with Operating Mode Switch in the

chargers, if any, or with the unit’s charger.

unit remains in shutdown mode after several attempts

“AUTO/REMOTE” position.

 

to reset, contact Tripp Lite Customer Service for assistance.

Red “LOW” Battery Indicator Light is

Battery voltage is low. Unit has shut down to protect battery

If AC power (utility- or generator-supplied) is present, the unit will

flashing with Operating Mode Switch in the

from damage.

automatically reset itself and start recharging connected batteries.

“AUTO/REMOTE” position.

 

However, if an external charger is used to recharge the batteries,

 

 

 

you will need to manually reset the unit by moving the Operating

 

 

 

Mode Switch to “OFF” for two seconds then returning it to

 

 

 

“AUTO/REMOTE”.

 

 

False reading due to undersized or insufficiently connected

Use sufficient size DC cable sufficiently connected to UPS System.

 

 

DC cabling.

 

 

Red “LOAD” Operation Indicator Light

Inverter is overloaded. Unit will automatically shut down after

Reduce load. Reset by moving Operating Mode Switch to “OFF”.

flashing

5 seconds.

Wait 1 minute. Switch to “AUTO/REMOTE”.

* User-supplied.

 

 

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

This product designed and engineered in the USA.

12T

200409045 93-2400

Image 12
Contents Contents Limited Warranty Warranty RegistrationService & Maintenance Important Safety Instructions Battery Connection WarningsLocation Warnings Equipment Connection WarningsFeature Identification MOVE-UPSSwitch Modes Indicator LightsResetting Your UPS System to Restore AC Power OperationConfiguration Set Configuration DIP SwitchesGroup a DIP Switches All Models Group B DIP Switches 1012 and 2012 Models Only Mounting Horizontal MountBattery Selection Select Battery TypeMatch Battery Amp-Hour Capacity to Your Application Battery Connection Is limited by the length and gauge of the cabling runningConnection for Models with Hardwire Terminals AC Input/Output ConnectionConnection for Models with Cords and Receptacles Troubleshooting Symptom Problems Corrections