Battery Replacement

Under normal conditions, the original battery in your UPS will last several years. Contact Tripp Lite for information about replacement batteries.

Battery replacement should be performed only by qualified service personnel. The batteries are hot-swappable: it is not necessary to turn off or disconnect the UPS and its connected load to replace the UPS’s batteries. However, when it is convenient to do so, service personnel may simplify the replacement procedure by turning power off at the UPS outlets by pressing the OFF switch to and disconnecting the UPS’s power cord from the wall outlet.

When replacing the batteries on a SU1000RTXL2U, SU1000RTXL2UHV or SUINT1000RTXL2U, qualified service personnel should refer to “Battery Warnings” in the Safety section and follow this procedure:

1)Place the UPS horizontal with the Control Panel on the right side.

2)Remove both snap-on cover panels (A).

3)Unscrew and remove rack handle plates (B) on either side of the UPS.

4)Disconnect the microprocessor circuit board plug (C) located on the right side of the UPS.

5)Disconnect battery connectors (D). Note: while batteries are disconnected, the UPS will not provide battery backup in the event of a power outage.

6)Unscrew and remove the battery retaining bracket (E).

7)Grasp pull-tab and pull out sliding battery tray (F).

8)Make a detailed sketch of the batteries and the polarity, color and connection of all cables. Disconnect used batteries and dispose of them properly. Connect replacement batteries in exactly the way the original batteries were connected. Note: Small sparks arcing between battery connectors during battery replacement are normal. Reassemble the UPS by reversing steps 1-7. Note: you may not receive full runtime until your new batteries have fully charged.

D

C

F

A

E

B

SU1000RTXL2U shown

12

Image 12
Contents SmartOnline Th Street Chicago, IL 60609 USAImportant Safety Instructions UPS Location WarningsRackmount MountingPlug your UPS’s line cord into an electrical outlet Connection and Start-UpSerial Port Connection Optional ConnectionsFront Panel Switches Front Panel Indicator LightsBasic Operation Rear Panel Communications Check the utility line for wiring problems Restart the UPS. If the problem persistsThis indicates that utility power is too high Or low for the UPS to operate in BypassSU1000RTXL2U shown SU2200RTXL2U shown Service StorageSU3000RTXL3U SU3000RTXL3UHV SUINT3000RTXL3U Manual del usuario Th Street Chicago, IL 60609 EE.UUImportantes instrucciones de seguridad Guarde Estas InstruccionesMontaje en bastidor MontajeEnchufe su equipo al sistema UPS Conexión y encendidoConexión de puerto serial Conexiones opcionalesInterruptores del panel frontal Luces indicadoras del panel frontalOperación básica continuación Luces indicadoras del panel frontal continuaciónOperación básica continuación Panel posterior continuación Condición Error de Eeprom Condición Reemplazar bateríaEncendidas Batería BAJA, EN Batería Condición Batería bajaLocalización de fallas continuación Se muestra SU1000RTXL2U Reemplazo de la batería continuación Almacenamiento ServicioEspecificaciones continuación Guide de lutilisateur Th Street, Chicago, IL 60609 USAImportantes consignes de sécurité Conservez CES Instructions EN UN Lieu SÛRMontage en bâti MontageInstallation suite Connexion et démarrageConnexion de port série Connexions facultativesCommutateurs du panneau avant Voyants du panneau avantExploitation de base suite Voyants du panneau avant suiteVoyants du panneau avant suite Panneau arrière Panneau arrière suite Communiquez avec le service à la Allumés Fault DéfaillanceClignotent Fault Défaillance Allumés FAULT, Replace BattDépannage suite Modèle SU1000RTXL2U illustré Remplacement des batteries suite Entreposage EntretienSpécifications suite SU3000RTXL3U SU3000RTXL3UHVÐóêîâîäñòâî ïîëüçîâàòåëÿ Âàæíûå óêàçàíèÿ ïî òåõíèêå áåçîïàñíîñòè Ñîõðàíèòå ÝÒÓ ÈíñòðóêöèþÓñòàíîâêà Óñòàíîâêà â ñòîéêåÏîäêëþ÷èòå êàáåëü ýëåêòðîïèòàíèÿ ÈÁÏ ê ðîçåòêå Ñîåäèíåíèå ñ ïîñëåäîâàòåëüíûì ïîðòîì Îñíîâíûå îïåðàöèè Load Active MeterÎñíîâíûå îïåðàöèè ïðîäîëæåíèå Îñíîâíûå îïåðàöèè ïðîäîëæåíèå Çàäíÿÿ ïàíåëü ïðîäîëæåíèå Ïîèñê è óñòðàíåíèå íåèñïðàâíîñòåé Ïîèñê è óñòðàíåíèå íåèñïðàâíîñòåé ïðîäîëæåíèå Çàìåíà áàòàðåé Çàìåíà áàòàðåé ïðîäîëæåíèå Õðàíåíèå è òåõîáñëóæèâàíèå Òåõíè÷åñêèå õàðàêòåðèñòèêèÒåõíè÷åñêèå õàðàêòåðèñòèêè ïðîäîëæåíèå SU3000RTXL3U SU3000RTXL3UHV SUINT3000RTXL3U
Related manuals
Manual 5 pages 32.44 Kb

SU1500RTXL2UHV, SUINT1500RTXL2U, SU1500RTXL2U specifications

The Tripp Lite SU1500RTXL2U is a versatile and reliable uninterruptible power supply (UPS) designed to provide protection for critical electronic equipment in various environments. With a power capacity of 1500 VA and a power output of 1000 Watts, this UPS is ideal for small servers, network equipment, and other sensitive devices that require consistent and uninterrupted power.

One of the standout features of the SU1500RTXL2U is its ability to offer extended runtime configurations. The unit includes a built-in battery, but it is also compatible with additional external battery packs that can be connected to prolong the UPS's runtime during power outages. This capability is particularly useful for businesses that cannot afford downtime and require extended periods of operation during an electrical failure.

Equipped with line-interactive technology, the SU1500RTXL2U provides reliable voltage regulation. It automatically adjusts voltage levels to maintain optimal power supply conditions, ensuring that connected devices receive a stable output. This feature significantly reduces the risk of damage from power surges, sags, and other irregularities.

Additionally, this Tripp Lite model features eight NEMA 5-15R outlets, allowing multiple devices to be connected simultaneously. It provides a combination of battery backup and surge protection, safeguarding equipment against potential damage from power spikes or outages. The UPS also includes an LCD screen that offers real-time information on battery status, load capacity, and input/output voltages, enabling users to monitor performance easily.

The SU1500RTXL2U is designed with user-friendliness in mind. Its compact 2U rack-mountable form factor facilitates easy installation in standard network racks or server rooms. The built-in smart management software ensures seamless integration with most operating systems, allowing users to configure settings and monitor the UPS through their computers.

Furthermore, the SU1500RTXL2U is equipped with an automatic voltage regulation (AVR) feature, enabling it to maintain consistent output voltage levels without draining the battery. This not only enhances operational efficiency but also extends the lifespan of the unit's batteries.

In conclusion, the Tripp Lite SU1500RTXL2U is an exceptional UPS solution equipped with essential features that ensure the reliability and stability of power supply for sensitive equipment. Its extended runtime options, line-interactive technology, and user-friendly design make it an indispensable asset for any organization relying on uninterrupted power.