Troubleshooting (continued)
Lights (On/Flashing) and Condition | Solution |
On: FAULT, BYPASS, LINE, 100%, 75% | Check the UPS to be sure that there is |
Condition: On Bypass due to High | adequate space for air to circulate near |
Internal Temperature | the vents and that the fan is working |
| properly. Restart the UPS. |
Flashing: LINE | This indicates that utility power is too high |
Condition: Input Abnormal | or low for the UPS to operate in BYPASS |
| mode, so if an inverter failure occurs, |
| the UPS will deliver no output. |
On: FAULT, 100%
Flashing: LINE, BYPASS
Condition: No Output due to High Output Voltage and Abnormal Input
Restart the UPS. If the problem persists, contact Tripp Lite for repairs.
Flashing: LINE, BYPASS
On: FAULT, 75%
Condition: No Output due to Low Output Voltage and Abnormal Input
Restart the UPS. If the problem persists, contact Tripp Lite for repairs.
Flashing: LINE, BYPASS
On: FAULT, 50%
Condition: No Output due to High Bus Voltage and Abnormal Input
Restart the UPS. If the problem persists, contact Tripp Lite for repairs.
Flashing: LINE, BYPASS
On: FAULT, 25%
Condition: No Output due to Low Bus Voltage and Abnormal Input
Restart the UPS. If the problem persists, contact Tripp Lite for repairs.
Flashing: LINE, BYPASS
On: FAULT, 100%, 75%
Condition: No Output due to High Internal Temperature and Abnormal Input
Check the UPS to be sure that there is adequate space for air to circulate near the vents and that the fan is working properly. Restart the UPS. If the problem persists, contact Tripp Lite for repairs.