Tripp Lite 2-9USTAND UPS Power ON, UPS Self-Test, Alarm Silence, UPS Cold Start, Basic Operation

Page 7
UPS Power ON

Basic Operation

Front Panel Switches

“ON/TEST” Button: This switch controls four separate UPS functions:

UPS Power ON

To turn the UPS on, press this button, hold it for several seconds until you hear a beep, then release it. The “ON LINE” LED will illuminate.

UPS Self-Test

During normal on-line operation, press this button and hold it until you hear a beep. This initiates a 10-second self-test of the battery. The UPS will shift to battery power (all LEDs will illuminate) for ten seconds.

Alarm Silence

To silence the UPS “on-battery” alarm, press this button and hold it until you hear a beep.

UPS Cold Start

To use your UPS as a stand-alone power source when AC power is unavailable (i.e. during a blackout), press this button and hold it until you hear a beep. The UPS will then provide battery power to its outlets.*

*The “ON BATT” Indicator Light will be illuminated since your UPS will be operating from battery power.

“OFF” Button: This button turns power OFF at the UPS receptacles. Press this switch, hold it until you hear a beep, then release it. The UPS will continue charging and the fan will continue to cool internal components even after you turn the UPS receptacles off. To turn the UPS OFF completely, including the charger, disconnect the UPS’s power cord after pressing the “OFF” switch.

Front Panel Indicator Lights

“ON LINE” LED: This green light will illuminate constantly to indicate the UPS is performing normal on-line operation (filtering and resynthesizing incoming AC line voltage to provide pure sine wave output). When this light is illuminated, you can monitor the load level of your UPS on the “LOAD ACTIVE METER” LEDs.

“LINE” LED: This green light will illuminate constantly to indicate the utility supplied AC line voltage at your wall outlet is nominal. It will flash if the line voltage is outside the nominal range (either too low or two high). No action is required on your part when the LED flashes; the UPS continuously and automatically filters AC line power to provide your equipment with pure sine wave AC power, regardless of brownout or overvoltage conditions. If this light is off, then AC line voltage is not present (blackout) or is at an extremely high voltage, and the UPS will provide connected equipment with power from battery.

7

Image 7
Contents Battery Replacement Important Safety InstructionsInstallation TroubleshootingUPS Connection Warnings Battery WarningsSAVE THESE INSTRUCTIONS UPS Location WarningsMounting Rack 4-Post Mounting2-Post Telecom Mounting Installation continuedMounting Tower 3 Turn your UPS ON InstallationImporant continuedSafety Instructions1 Plug your UPS’s line cord into an electrical outlet 2 Plug your equipment into your UPS3 EPO Port Connection all models 4 External Battery Connection2 USB and RS-232 Serial Communications all modelsUPS Cold Start UPS Power ONAlarm Silence UPS Self-TestFront Panel Indicator Lights continued Basic Operation continuedExternal Battery Pack Connector configuration varies by model Use to connect optional Tripp Lite Battery Packs for additional runtime. Contact Tripp Lite Customer Support at 773 869-1234 for the appropriate Tripp Lite battery pack to connect. Refer to instructions available with the Battery Pack for complete connection information and safety warnings Communications Rear Panel continuedapplications Troubleshooting or low for the UPS to operate in BYPASS Troubleshooting continuedThis indicates that utility power is too high adequate space for air to circulate near6 Replace Front Panel Procedure1 Remove Front Panel 2 Disconnect Batteries 3 Remove/Dispose of Batteries 4 Add Batteries 5 Connect BatteriesStorage Service773.869.1234 USA 773.869.1212 International 1111 W. 35th Street, Chicago, IL 60609 USA200811139 93-2471EN