Moxa Technologies 6110 user manual

Page 34

Modbus Settings

Setting

Value

 

Notes

 

Modbus RTU Slave1

 

Set the Modbus type of the

 

Modbus ASCII Slave

2

Attached Serial Device type

 

serial device attached to

Modbus RTU Master3

 

NPort 6110’s serial port.

 

Modbus ASCII Master4

 

 

 

 

NPort Modbus Gateway

 

100 to 3276 ms;

 

provides this setting for

Initial delay time

 

those PLCs that need a

default = 100 ms

 

 

 

longer time for their

 

 

 

 

 

 

system to be initialized.

Modbus/TCP Slave device setting

 

 

 

IP address assigned to

Valid when the attached

Remote Modbus Slave IP

the remote Modbus

 

serial device is a Modbus

 

slave device.

 

RTU/ASCII Master.

 

default = 502

 

Set this value to 0 (zero) to

TCP Port No.

 

disable the corresponding

 

 

 

Modbus/TCP slave device.

 

1 to 247

 

The unique Modbus ID

ID No. Range

 

number assigned to the

 

 

 

Modbus device.5

Additional Information

1.When the serial Modbus device is running in Modbus/RTU Slave mode, the NPort Modbus Gateway is ready to connect automatically to Modbus/TCP Master devices. Up to 7 Modbus/TCP master devices can connect to one serial Modbus slave device.

2.Modbus ASCII Slave mode works the same as Modbus/RTU slave mode, except that the data format is Modbus/ASCII.

3.When the serial Modbus device is running in Modbus/RTU Master mode, the NPort Modbus Gateway is ready to connect automatically to Modbus/TCP slave devices. You will also need to configure the IP address for up to 4 Modbus/TCP slave devices that can be connected to over the Ethernet network.

4-8

Image 34
Contents NPort 6110 Modbus/TCP To Serial Communication Gateway Page NPort 6110 Modbus/TCP To Serial Communication Gateway Page Moxa Internet Services Page Table of Contents Page Introduction OverviewFeatures Powerful operation modes for versatile Modbus applicationsProduct Specifications LANPackage Checklist EnvironmentalFront/Top/Rear/Bottom Panel Views Page Serial Installation Power ConnectionGetting Started Ethernet Installation Software InstallationPage Page Page Page Housing DIN-RailWall Mount Typical Modbus Applications Connect all Modbus devices over the Ethernet network… Link the Serial Master device with Ethernet Slave devices… Page Configuring Modbus Gateway Starting Modbus Gateway Configurator Broadcast Search Searching for NPortSpecify by IP Address Modify Configuration Network Settings Modbus Settings AlphanumericPage Page Advanced Modbus Settings IP address Page Modbus Serial Settings RTS/CTS Uart Fifo Password Other Functions Upgrade FirmwareUnlock Page Remote Monitoring and Management Start Log MonitorPage Troubleshooting ID No. mismatchPage Pin Assignments DB9 Male PinoutsPage Declaration of Conformity Page Problem Report Form NPort 6110 Modbus GatewayReturn Procedure