Advanced Modbus Settings

Setting

Value

Notes

 

Enable (Default)

Select Enable when

Auto Slave Unit ID

multiple Modbus devices

 

 

are accessible at the same

Disable

 

 

IP address.

1

 

 

 

 

10 to 3000 ms

This parameter is active

Character Timeout

when the attached serial

(default = 100 ms)

device is set to

 

 

Modbus/RTU.2

 

 

Allows you to configure

 

10 to 3000 ms

the message timeout for

Message Timeout

communication between

(default = 1000 ms)

 

connected Ethernet or

 

 

 

 

serial Modbus devices.

 

 

This parameter is active

 

 

when the Modbus

Modbus/TCP Exception

default = 502

Gateway connects a

Modbus/TCP Master with

 

 

 

 

Modbus serial slave

 

 

devices.3

 

Additional Information

1.Modbus/TCP protocol contains a “Unit ID” field to identify multiple Modbus slave devices accessible at a single IP address. When the Modbus/TCP command contains a Unit ID, the Modbus Gateway can pass the Unit ID to Modbus serial devices. This allows you to link to multiple serial devices with a Modbus Gateway. Some PLCs assume that each IP connects to only one device. In these cases, the Unit ID can be set “0,” but you must manually assign a Unit ID (between 1 and 247) to the connected serial device. However, each Modbus Gateway can connect to only one serial device.

This setting is valid when [Attached Serial Device type] is set to [Modbus RTU Slave ] or [Modbus ASCII Slave].

Enable: Uses the Unit ID in the Modbus/TCP packet. This is the default setting.

Disable: Uses the predefined Unit ID instead of Modbus/TCP’s.

ID:

The predefined Unit ID value, ranging from 1 to 247, which is valid

4-10

Image 36
Contents NPort 6110 Modbus/TCP To Serial Communication Gateway Page NPort 6110 Modbus/TCP To Serial Communication Gateway Page Moxa Internet Services Page Table of Contents Page Introduction OverviewFeatures Powerful operation modes for versatile Modbus applicationsProduct Specifications LANPackage Checklist EnvironmentalFront/Top/Rear/Bottom Panel Views Page Power Connection Serial InstallationGetting Started Ethernet Installation Software InstallationPage Page Page Page Housing DIN-RailWall Mount Typical Modbus Applications Connect all Modbus devices over the Ethernet network… Link the Serial Master device with Ethernet Slave devices… Page Configuring Modbus Gateway Starting Modbus Gateway Configurator Searching for NPort Broadcast SearchSpecify by IP Address Modify Configuration Network Settings Modbus Settings AlphanumericPage Page Advanced Modbus Settings IP address Page Modbus Serial Settings RTS/CTS Uart Fifo Password Upgrade Firmware Other FunctionsUnlock Page Remote Monitoring and Management Start Log MonitorPage Troubleshooting ID No. mismatchPage Pin Assignments DB9 Male PinoutsPage Declaration of Conformity Page Problem Report Form NPort 6110 Modbus GatewayReturn Procedure