Moxa Technologies 6110 user manual Troubleshooting, ID No. mismatch

Page 45

5

Troubleshooting

In this chapter, we give answers to some common troubleshooting questions related to Modbus Gateway applications.

1. ID No. mismatch

ID number mismatch is the most common field installation problem encountered. First, make sure the ID number of each Modbus device corresponds to the settings in the automation software on the computer. Pay attention to Modbus Gateway’s configuration to avoid ID number issues.

1.1When [Attached Serial Device] is set to [Modbus/RTU Slave] or [Modbus/ASCII Slave], and the [Auto Slave Unit ID] is disabled, the Modbus Gateway will use a fixed ID number. Make sure the ID number of the serial device is identical to the settings in the Modbus Gateway.

1.2When [Attached Serial Device] is set to [Modbus/RTU Master] or [Modbus/ASCII Master], the Modbus Gateway replies on [ID No. Range] to transfer the serial Modbus device command to the IP address of the correct Modbus/TCP device. The ID number in the Ethernet device and Modbus/TCP slave device setting table must match.

2. Modbus Address configuration error

Basically, Modbus Gateway will not change the Modus address in the data packet of the protocol. When your automation software or device reports address error, check that the address setting on the device is correct.

3. Proper character timeout configuration for Modbus/RTU

A Modbus/RTU device requires character timeout for data packet segmentation. When a CRC error occurs, you may need to increase the character timeout in Modbus Gateway.

4. HMI polling time and timeout interval issue

When [Attached Serial Device] is set to [Modbus/RTU Slave] or [Modbus/ASCII Slave], each Modbus Gateway accepts up to 7 connections from Modbus/TCP master devices. However, the Ethernet speed is much higher than the Serial speed. Therefore, proper polling time and timeout interval settings are required to prevent timeout error. For a particular HMI monitoring system, the best configuration is: polling time set to 0.5 – 1.0 sec, Timeout interval 3 sec.

5-1

Image 45
Contents NPort 6110 Modbus/TCP To Serial Communication Gateway Page NPort 6110 Modbus/TCP To Serial Communication Gateway Page Moxa Internet Services Page Table of Contents Page Overview IntroductionPowerful operation modes for versatile Modbus applications FeaturesLAN Product SpecificationsEnvironmental Package ChecklistFront/Top/Rear/Bottom Panel Views Page Power Connection Serial InstallationGetting Started Software Installation Ethernet InstallationPage Page Page Page DIN-Rail HousingWall Mount Typical Modbus Applications Connect all Modbus devices over the Ethernet network… Link the Serial Master device with Ethernet Slave devices… Page Configuring Modbus Gateway Starting Modbus Gateway Configurator Searching for NPort Broadcast SearchSpecify by IP Address Modify Configuration Network Settings Alphanumeric Modbus SettingsPage Page Advanced Modbus Settings IP address Page Modbus Serial Settings RTS/CTS Uart Fifo Password Upgrade Firmware Other FunctionsUnlock Page Start Log Monitor Remote Monitoring and ManagementPage ID No. mismatch TroubleshootingPage DB9 Male Pinouts Pin AssignmentsPage Declaration of Conformity Page NPort 6110 Modbus Gateway Problem Report FormReturn Procedure