Schneider Electric SURTD 3000 manual XLJ models

Page 10

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

 

 

Low Bypass Point

 

Output Voltage Setting

Minimum voltage that the UPS

 

160 VAC

200 VAC:

 

will pass to connected

 

 

160 - 185 VAC

 

equipment during internal

 

 

 

bypass operation.

 

 

208 VAC:

 

 

 

 

 

 

 

160 - 190 VAC

 

 

 

 

220 VAC:

 

 

 

 

160 - 195 VAC

 

 

 

 

230 VAC:

 

 

 

 

160 - 200 VAC

 

 

 

 

240 VAC:

 

 

 

 

160 - 205 VAC

 

 

 

 

 

 

 

Output Voltage

XLJ models:

200, 208, 220,

 

Allows the user to select the on

 

200 VAC

230, 240 VAC

 

on-line output voltage.

 

XLT models:

 

 

 

 

208 VAC

 

 

 

 

XLTW models:

 

 

 

 

220 VAC

 

 

 

 

XLI models:

 

 

 

 

230 VAC

 

 

 

 

 

 

 

 

Output Frequency

Automatic

50 ± 3 Hz

60 ± 3 Hz

Sets the allowable UPS output

 

50 ± 3 Hz or

50 ± 1 Hz

60 ± 1 Hz

frequency. Whenever possible,

 

50 ± 0.1 Hz

60 ± 0.1 Hz

the output frequency tracks the

 

60 ± 3 Hz

 

50 ± 3 Hz or 60 ± 3 Hz

input frequency.

 

 

 

 

 

 

 

Number of External

0

0 to 100

 

Defines the number of external

Battery Packs

 

 

 

connected battery packs for

 

 

 

 

proper run time prediction.

 

 

 

 

Bypass Acceptable

Not required

Required/ Not required

Phase and frequency lock

 

 

 

 

required/not required before the

 

 

 

 

UPS will switch to bypass.

 

 

 

 

 

10

Image 10
Contents Smart-UPSRT Introduction SpecificationsInstallation UnpackingWiring and Connecting the UPS Connecting the Battery Modules and Attaching the Front Bezel Normal bypass Avoid using extension cords Troubleshooting in this manual OperationDoes not affect the voltage display User Configurable Items ON, OFFXLJ models Connecting the EPO Emergency Power OFF Option Terminal Mode to Configure UPS Parameters VA models Page Replacing the Battery Module Maintenance and TransportDisconnecting the Battery for Transport TROUBLESHOOTING, SERVICE, and Warranty Information Bypass LED Illuminates Service Limited WarrantyAPC Worldwide Customer Support Radio Frequency Warnings