NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES |
| ||
|
|
| ||
Low Bypass Point |
| Output Voltage Setting | Minimum voltage that the UPS | |
| 160 VAC | 200 VAC: |
| will pass to connected |
|
| 160 - 185 VAC |
| equipment during internal |
|
|
| bypass operation. | |
|
| 208 VAC: |
| |
|
|
|
| |
|
| 160 - 190 VAC |
|
|
|
| 220 VAC: |
|
|
|
| 160 - 195 VAC |
|
|
|
| 230 VAC: |
|
|
|
| 160 - 200 VAC |
|
|
|
| 240 VAC: |
|
|
|
| 160 - 205 VAC |
|
|
|
|
|
|
|
Output Voltage | XLJ models: | 200, 208, 220, |
| Allows the user to select the on |
| 200 VAC | 230, 240 VAC |
| |
| XLT models: |
|
|
|
| 208 VAC |
|
|
|
| XLTW models: |
|
|
|
| 220 VAC |
|
|
|
| XLI models: |
|
|
|
| 230 VAC |
|
|
|
|
|
|
|
|
Output Frequency | Automatic | 50 ± 3 Hz | 60 ± 3 Hz | Sets the allowable UPS output |
| 50 ± 3 Hz or | 50 ± 1 Hz | 60 ± 1 Hz | frequency. Whenever possible, |
| 50 ± 0.1 Hz | 60 ± 0.1 Hz | the output frequency tracks the | |
| 60 ± 3 Hz | |||
| 50 ± 3 Hz or 60 ± 3 Hz | input frequency. | ||
|
| |||
|
|
|
|
|
Number of External | 0 | 0 to 100 |
| Defines the number of external |
Battery Packs |
|
|
| connected battery packs for |
|
|
|
| proper run time prediction. |
|
|
|
| |
Bypass Acceptable | Not required | Required/ Not required | Phase and frequency lock | |
|
|
|
| required/not required before the |
|
|
|
| UPS will switch to bypass. |
|
|
|
|
|
10