Display Navigation

The display on the front of the meter provides status information for each

 

circuit, and general information for metering. The PowerLogic E4800 meter

 

has three buttons for navigating: a Display button, and left and right arrow

 

buttons. The display has a normal and a diagnostics mode.

 

Normal Mode

 

In Normal mode, the Display button scrolls through the information for each

 

meter. The left and right arrow buttons select the previous or next meter

 

points respectively.

 

The following information is available:

Real Energy Delivered kWh D

Real Energy Received kWh R

Real Power Watts

Reactive Energy Delivered KVarhD

Reactive Energy Received KVarhR

Reactive Power Var

VAh (Volt Amp hours)

VAs (Volt Amps)

In Normal mode, the right and left arrow buttons scroll the display from meter points 1 to 8, 1 to 12, or 1 to 24, depending on your configuration.

Diagnostics Mode

Diagnostics mode is accessed by pressing and holding the Display button for 5 seconds. In Diagnostics mode, pressing the Display button will scroll through the following information:

Real energy consumption in kWh

Real power in Watts

Apparent power in VA

Voltage

Current in amperes

Phase setting and CT rating in amperes

Local IP address

Send command

Set default IP address

Date and time (UTC)

In Diagnostics mode, the right and left arrow buttons scroll the display from meter 1 to 8, 1 to 12, or 1 to 24, depending on your configuration. When the local IP address is shown on the LCD, use the right and left arrow buttons to scroll through the following information:

Remote host IP address

4

© 2009 Schneider Electric All Rights Reserved

Image 10
Contents PowerLogicTM Series E4800 Hazard Categories and Special Symbols PowerLogicTM E4800 Series 930-112-01 02/2009PowerLogicTM E4800 Series PowerLogicTM E4800 Series 930-112-01 02/2009 Table of Contents Schneider Electric All Rights Reserved Powerlogic E4800 Configuration Tool Guide Configuration and ProgrammingProgramming access to meter parameters Parameter Read access Write access Activation timeManufacturing Meter and probe pointsDiagnostics Mode Normal ModeDisplay Navigation Direct Connection Ethernet Requirements Communications ConnectionsInjury Network Connection Ethernet Requirements Configuring the meter Login screenConfiguration tool main window Discovered Units dialog box Main configuration window with configured parameters Configuration parameters Field Parameter DescriptionReport Parameters Parameter Description By selecting the check box Daily Minutes List of supported metering configurations PowerLogic E4805 PowerLogic E4833 PowerLogic E4880Meter Point Configuration Meter Points Circuits TabBadge Numbering Badge Numbering pane Pulse Probes Tab Factor applied to the collected pulse countsCompleting the Meter Configuration E4800 meter is ready to be programmed. Proceed as followsSending the configured settings to the meter 930-112-01 Schneider Electric USA