TABLE 2-2 Cluster Platform Rack Components
Component | Quantity |
|
|
Sun StorEdge expansion cabinet | 1 |
Ethernet hub | 1 |
Netra T1 AC200 management server | 1 |
Netra st D130 boot disks | 4 |
Air baffle | 2 |
Sun Enterprise cluster node | 2 |
Sun StorEdge T3 array | 2 |
Terminal concentrator | 1 |
|
|
Power and Heating Requirements
The Cluster Platform 4500/3 hardware should have two dedicated AC breaker panels. The cabinet should not share these breaker panels with other, unrelated equipment. The system requires two
If the cabinet is installed on a raised floor, cool conditioned air should be directed to the bottom of each rack through perforated panels.
The
TABLE 2-3 Power and Heat Requirements for Cluster Platforms
Maximum Power Draw | Heat Dissipation | |
|
|
|
1 | 10480 W | 33786 BTUs/hr. |
|
|
|