TROUBLESHOOTING

#

Symptom

Possible Cause

What To Do

 

 

 

UPS will not turn on

On / Off / Test button not

Press the On button momentarily,

 

pushed

(one beep) to start UPS

 

 

 

UPS operates in

Input AC circuit breaker is

Reset circuit breaker by

battery mode only,

tripped

pressing the plunger back in. If

even though there is

 

the AC circuit breaker trips

normal AC present

 

after UPS starts up, reduce the

 

 

load on the UPS

Fault LED is

UPS has detected an internal

Call for service

illuminated

fault

 

 

 

 

The Site Wiring Fault

Incorrect service wiring

Have a qualified electrician

correct the service wiring

LED is illuminated

 

 

 

The On-line/On-

The UPS is being controlled

Disconnect the computer cable

from the UPS and press the On

Battery LED is

via its computer port

button momentarily. If UPS works

illuminated, but there

 

 

normally, software has control of

is no output

 

 

the UPS

 

 

UPS does not provide

The batteries may be weak or

Charge the batteries for 8 hours

expected backup time

at the end of useful service

and retest. If the backup time is

with internal batteries

life. The Battery Pack's circuit

still less than expected, the bat-

or with a Battery Pack

breaker maybe tripped

teries may need to be replaced,

 

 

even though the Weak/Bad

 

 

Battery LED is not illuminated.

 

 

Reset the Battery Pack's circuit

 

 

breaker

 

 

 

Weak/Bad Battery LED

Weak or bad batteries/bad bat-

Check battery connection/replace

is illuminated

tery connection

batteries. Follow battery replace-

 

 

ment procedures in section 6

UPS occasionally

Normal operation

The UPS is performing its intended

emits a beep

 

function

Battery Pack does not

DC circuit breaker tripped.

Reset the DC circuit breaker.

charge

The Battery Pack's internal fuse

Call for service

 

is blown

 

Overload LED is illumi-

The load has exceeded the

Check the specifications (see

nated and a constant

UPS's capacity

section 8). Remove part of the load

alarm

 

 

The On-Line LED is

The UPS is in either the Buck

The UPS is performimg its intended

blinking and the audible

mode or the Boost mode

function

alarm is silent

 

 

 

 

 

 

 

 

English

11

Image 12
Contents Page Table of Contents Important Safety Instructions IntroductionPara Systems Life Support Policy Controls and Indicators Front PanelInstallation Installation PlacementInstallation English Connecting to AN AC Source Computer Interface Connection OptionalTELEPHONE/NETWORK Surge Protection Connection Optional Charging the Battery Connecting Your EquipmentOperation Turning the Unit ON/OFFDIP Switch Settings AlarmsTroubleshooting Replacing the Battery Replacing the BatteryBattery Replacement Procedure Obtaining Service If the UPS Requires ServiceSpecifications 500VA 750VA 1100VA 1500VA 2300VA 3200 VASettings Function Factory Default User Choices DescriptionCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity English