Rackmount Solutions Enterprise Series manual Battery Replacement Procedure

Page 14

BATTERY REPLACEMENT PROCEDURE

PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot- swappable batteries, with the UPS on, the load will not be backed up.

NOTE: To Hot-Swap, skip to step number 6.

1.Turn off the equipment that is plugged into the output receptacles of the UPS.

2.Press and release, after one beep, the ON/OFF button on the front panel.

3.Turn off the AC circuit breaker on the rear panel of the UPS.

4.Unplug the UPS's AC power cord from the AC outlet.

5.Unplug the equipment from the output receptacles of the UPS.

6.Remove the front panel of the UPS.

7.Remove the four retaining screws and the battery retaining bracket.

8.Using the pull tab, pull the battery out (on the left hand side looking from the front). Do not pull the batteries out by pulling the battery jumper wires.

9.Disconnect the positive (red) wire from the battery positve terminal.

10.Remove the rest of the batteries, disconnect the battery jumper wires and the battery negative (black) wire from the battery negative terminal.

11.Reconnect the battery negative (black) wire to the battery negative terminal and the battery jumper wires. Verify proper polarity, negative (black) wire to the battery negative terminal and the battery jumper wires are connected properly.

12.Reinstall the batteries into the UPS, except for the battery on the left hand side of the UPS. Reconnect the battery positive (red) wire to the battery positive terminal. Some sparking may occur, this is normal. Verify proper polarity, reinstall the battery into the UPS.

13.Reinstall the battery retaining bracket and the retaining screws.

14.Reinstall the front panel of the UPS.

15.Dispose of the batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.

16.The UPS is now ready for the normal start-up procedure.

English

13

Image 14
Contents Page Table of Contents Important Safety Instructions IntroductionPara Systems Life Support Policy Controls and Indicators Front PanelInstallation Installation PlacementInstallation English TELEPHONE/NETWORK Surge Protection Connection Optional Connecting to AN AC SourceComputer Interface Connection Optional Operation Charging the BatteryConnecting Your Equipment Turning the Unit ON/OFFDIP Switch Settings AlarmsTroubleshooting Replacing the Battery Replacing the BatteryBattery Replacement Procedure Obtaining Service If the UPS Requires ServiceSpecifications 500VA 750VA 1100VA 1500VA 2300VA 3200 VASettings Function Factory Default User Choices DescriptionCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity English