Rackmount Solutions Enterprise Series Specifications, 500VA 750VA 1100VA 1500VA 2300VA 3200 VA

Page 16

SPECIFICATIONS

&

NOTE: 230Vac Specs Shown In ( )

500VA

 

750VA

 

1100VA

1500VA

 

2300VA

 

3200 VA

Acceptable input voltage

 

 

 

 

0 - 164 (0 - 290) Vac

 

 

 

Input voltage (on-line operation)

 

 

 

 

75 - 164 (150 - 290) Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage

 

 

 

 

105 - 128 (210 - 250) Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal input frequency

 

 

 

 

50 or 60 Hz, autosensing

 

 

 

Input protection

 

 

 

 

Resettable circuit breaker

 

Frequency limits (on-line operation)

 

 

 

 

50 or 60 Hz, +/-6Hz

 

 

 

Transfer time

 

 

 

 

<2 ms typical

 

 

 

Maximum load

500VA

 

750VA

 

1100VA

1500VA

 

2300VA

 

3200VA

 

300W

 

450W

 

660W

900W

 

1380W

 

1920W

On-battery output voltage

Default 117 (225) Vac / User selectable at 108,113.117 (215,225,235) Vac

On-battery frequency

50 or 60 Hz, +/-.5 Hz, unless synchronized to utility during brownout

On-battery waveshape

 

 

 

 

True Sine Wave

 

 

 

Protection

Overcurrent and short circuit protected, latching shutdown on overload

Surge energy rating

 

 

 

 

500 J (440J)

 

 

 

 

 

500 J (440J)

(one time, 10/1000 us waveform)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge current capability

 

 

 

6.5 kAmps total

 

 

 

13 kAmps total

(one time, 8/20 us waveform)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge response time

 

 

0 ns (instantaneous) normal mode; <5 ns common mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge voltage let-through

 

<5%

 

 

 

 

 

 

<0.5%

 

 

(percentage of applied ANSI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C62.41 Cat. A +/-6kV test waveform)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise filter

 

 

Normal and common mode EMI/RFI suppression

 

Battery Type-Spill proof, maintenance free,

Two 12 V

 

Two 12 V

 

Four 12 V

 

Four 12 V

 

 

Four 12 V

 

Four 12 V

user replaceable, sealed lead-acid

4.5 Ah

 

7.2 Ah

 

4.5 Ah

 

7.2 Ah

 

 

12 Ah

 

12 Ah

Typical battery life

3 to 6 years, depending on the number of discharge cycles and ambient temp.

Typical recharge time

 

 

 

 

2 to 5 hours from total discharge

 

10 Base-T surge protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

let-through (as a percentage of an

 

 

 

 

 

 

<5%

 

 

 

 

 

 

 

applied +/-6 kV 1.2/50 us, 500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Telephone line surge protection let-through

 

 

 

 

 

 

 

(as a percentage of an applied +/-6 kV

 

 

 

<1%

 

 

1.2/50 us, 500 a 8/20 us test)

 

 

 

 

 

 

 

Operating temperature

 

0 to 40 degrees C (+32 to 104 degrees F)

 

Storage temperature

 

-15 to +45 degrees C (+5 to +113 degrees F)

 

Operating and storage relative humidity

 

 

0 to 95%, non-condensing

 

 

Operating elevation

 

 

0 to +3,000 m (0 to + 10,000 ft)

 

Storage elevation

 

 

0 to +15,000 m (0 to +50,000 ft)

 

 

 

 

 

 

 

 

Electromagnetic immunity

 

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

 

 

 

 

 

 

 

 

 

Audible noise at 1 m (3 ft.)

 

 

 

<45 dBA

 

 

Size (H x W x D) in Rackmount and

 

3.5 x 17 x 16"

 

 

5.25 x 17 x 16"

Desktop Configuration

 

 

 

 

(8.9 x 43.2 x 40.7) cm

(13.4 x 43.2 x 40.7) cm

 

 

 

 

 

 

 

 

 

43(49)lb

52(58)lb

57(62)lb

 

74(80)lb

88(94)lb

95(101)lb

Weight - Net (Shipping)

19.5(22)Kg

23.5(26)Kg

25.5(28)Kg

33.5(36)Kg

40(42.5)Kg

43(45.5)Kg

 

 

 

 

 

 

 

Safety and approvals

 

UL1778, CSA 22.1, CE EMC, CE SAFETY, TUV

 

 

 

 

 

 

 

 

EMC Verification

 

 

FCC Class B certified

 

 

English

15

Image 16
Contents Page Table of Contents Important Safety Instructions IntroductionPara Systems Life Support Policy Controls and Indicators Front PanelInstallation Installation PlacementInstallation English Computer Interface Connection Optional Connecting to AN AC SourceTELEPHONE/NETWORK Surge Protection Connection Optional Charging the Battery Connecting Your EquipmentOperation Turning the Unit ON/OFFDIP Switch Settings AlarmsTroubleshooting Replacing the Battery Replacing the BatteryBattery Replacement Procedure Obtaining Service If the UPS Requires ServiceSpecifications 500VA 750VA 1100VA 1500VA 2300VA 3200 VASettings Function Factory Default User Choices DescriptionCustomized Output Receptacle Panels Limited Product Warranty Limited Product WarrantyDeclaration of Conformity English