| CONFIGURABLE PARAMETERS |
' | AND SETTINGS |
|
(These items require optional software or hardware)
FUNCTION | FACTORY DEFAULT | USER CHOICES |
| DESCRIPTION | |
|
|
|
| ||
UPS ID | Enterprise Series | Up to 64 characters to | Use this function to uniquely | ||
|
| define the UPS | identify the UPS in your net- | ||
|
|
| work configuration | ||
|
|
|
| ||
Battery install | Date of manufacture | Date of battery re- | Enter the current date when | ||
date |
| placement - | replacing batteries | ||
|
| day/month/year |
|
|
|
|
| XX/XX/XXXX |
|
|
|
|
|
|
| ||
Battery life in | 1826 | Up to 5 characters | At first battery replacement, | ||
days |
|
| reset to reflect actual num- | ||
|
|
| ber of days experience in | ||
|
|
| your environment or leave | ||
|
|
| factory default. | ||
|
|
|
| ||
Enable/ | Enabled | Enable or disable | When enabled, the UPS will | ||
Disable auto |
|
| automatically restart from a | ||
restart |
|
| low | battery | shutdown |
|
|
| when normal AC returns | ||
|
|
|
| ||
Set audible | Enabled | Enabled, at low bat- | Enabled - the UPS will emit | ||
alarm state |
| tery, disabled | a short beep when in the | ||
|
|
| battery mode. At Low Bat- | ||
|
|
| tery | the UPS will emit two | |
|
|
| tones from | low battery | |
|
|
| warning until shutdown. | ||
|
|
| Disabled - Use only when | ||
|
|
| software is controlling the | ||
|
|
| UPS or to silence the alarm | ||
|
|
|
| ||
Shutdown | UPS output | UPS output or UPS | UPS Output - When the UPS | ||
Type |
|
| is told to shut down, it turns | ||
|
|
| off the UPS output only. UPS | ||
|
|
| - Turns off the UPS which | ||
|
|
| requires the UPS to be | ||
|
|
| turned on manually | ||
|
|
|
| ||
Set inverter | 117Vac | 108, 113, 117Vac | changes output voltage | ||
output voltage | ( 225)Vac | (215, 225, 235)Vac | during battery mode opera- | ||
|
|
| tions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
16