Mitsubishi Electronics 2033C technical manual AC input User supplied

Page 12

MITSUBISHI

2033C SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-6

FIGURE 1.2 Single Line Diagram - Bypass Operation. Load fed through static bypass line.

CB

AC input

User supplied

 

Maintenance

Static Transfer

Bypass

Switch

Switch

CB3

CONVERTER INVERTER

 

 

 

Output

CB1

FI

FO

52C

FB

 

52CS(7.5-20kVA)

 

52MB&52L(30-50kVA)

 

 

CB2

 

Power Flow

 

 

BATTERY

 

Not in Use

 

 

 

40kVA, 50kVA:

UPS Module

 

External Battery

 

 

Referring to Figure 1.2, the Internal Static Bypass line is a Hard wired line through CB3 which supplies the critical load with unconditioned input power. The purpose of this line is to route power to the critical load while the UPS module is de-energized (converter and inverter), and during Start-up before the system is fully operational.

The internal control system determines the operation of the two paths, with the load powered from the inverter being the normal operation.

Referring to Figure 1.3, if the input power is interrupted, the battery will immediately supply the DC power required by the Inverter to maintain continuous AC power to the load. A fully charged battery will provide power for the specified time at the rated load, or longer at reduced load.

When power is restored after a low battery shutdown, the Converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. The load is assumed by the inverter automatically without operator intervention.

In the event of a power failure, the Converter will de-energize and the batteries will discharge into the Inverter and maintain power to the critical load until a) the battery capacity expires and the inverter turns off, or b) input power is restored after which the converter will power the inverter and simultaneously recharge the batteries. Figure 1.3 illustrates the flow diagram during battery operation.

MITSUBISHI ELECTRIC 2033C SERIES UPS

Image 12
Contents 2033C Series Owners / Technical Manual Mitsubishi 2033C Series UPS NumberElectric Owners / Technical Manual Table of Contents List of Tables IiiSingle Line Diagram UPS on Maintenance Bypass Operation List of FiguresHow to use this Manual Important Safety Instructions Retain These Instructions Electric Owners / Technical Manual IntroductionMitsubishi 2033C Series UPS Electric Owners / Technical Manual General Mitsubishi 2033C Series UPS Overview AC input User supplied Single Line Diagram Battery Operation Transfer of load from inverter to maintenance bypass Transfer of load from maintenance bypass to inverter5a UPS Parts Location7.5-20kVA SWM RYDR-X Relay PCB RYDR-X board Signal I/F on RYDR-X board Figure LCD Touch Panel Monitor DisplayExternal contact signal terminal block Reset switch for Service Personnel onlySpecifications UPS Cable Width Depth Height Weight Heat LossKVA EntryAC Input Characteristics BatteryAC Output EnvironmentalComponent Description Component Rating @ 208V,3 phase, 60 Hz Rating of Contactors and FusesLCD Touch Panel Monitor Display and Keypad Main Menu ScreenMain Menu Screen Battery Measurement Screen Measurement ScreensAC Input Measurement Screen AC Output Measurement ScreenElectric Owners / Technical Manual Fault Display Screen Fault Display ScreenBattery operation BAT OP. yellow Alarm Silence Silence gray10Emergency Power Off EPO red 11Load on maintenance bypass MBP redExternal Signal Terminal Block OverloadOutput Contacts for external alarm annunciation Terminals 11 to 12 Battery Operation contactTerminals 7 to 8 Load on Inverter contact Input Contacts for remote access of UPS Terminals 3 to 4 Battery Temp. High contact inputExternal communication connector SUB 9Pin maleInstallation and Operation Transportation and InstallationMitsubishi 2033C Series UPS Electric Owners / Technical ManualInstallation Procedure Space requirement for routine maintenanceBattery Minimum clearance required for ventilationMitsubishi 2033C Series UPS RED Burndy UPS Terminal Designation Input/Output Power Terminals 7.5kvA 20kVA NumberDC Input Power Terminal MBSRYDR-X C N a B C NMBS AC Input AC Output DC Input Grounding barRYDR-X Operating Procedures UPS Start-up Procedure UPS Shutdown ProcedureEPO Emergency Power Off Procedure UPS Fault Electric Owners / Technical Manual Response to UPS FailureElectric Owners / Technical Manual Parts Replacement UPS Component PartsElectric Owners / Technical Manual Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Transfer circuit abnormal Call service engineer Mitsubishi 2033C Series UPS Warranty & Out of warranty Service Mitsubishi Electric Automation IncRegister UPS for Warranty Address Change Mitsubishi Electric Automation, IncCustomer Information