The two positions are identified as NORMAL and BYPASS. In the NORMAL position the load is fed by the UPS - either through the inverter or through the static bypass line. In the BYPASS position the load is powered by an external source such as the utility or a generator. This transfer operation must be made while the UPS is in the static bypass mode.

The transfer procedure to place the UPS in maintenance bypass mode, or from bypass mode to normal operation mode is outlined below:

A)Transfer of load from inverter to maintenance bypass

1.On the front panel, press the "STOP" button. The “BYP.OP.” LED illuminates within 3 seconds.

2.After confirming that the “BYP.OP.” LED is illuminated, Rotate MBS(52CS/SWM) clockwise to the “TRANSFER” position (Do not rotate 52CS/SWM if the “BYP.OP.” LED is NOT illuminated).

3.After 3 seconds, rotate 52CS/SWM clockwise to the “BYPASS” position.

4.Transfer complete. Load is now powered from the external source. UPS can be shutdown.

B)Transfer of load from maintenance bypass to inverter

1.Rotate 52CS/SWM counterclockwise from the “BYPASS” position to the “TRANSFER” position, wait 5 seconds.

2.On the UPS, confirm the “BYP.OP.” LED is illuminated. If not, press the “STOP” button.

3.Rotate 52CS/SWM counterclockwise to the “NORMAL” position.

4.On the UPS, press the “START” button. The “INV.OP.” LED should illuminate.

5.Transfer complete. Load now powered by the inverter.

MITSUBISHI ELECTRIC 2033C SERIES UPS

Image 14
Contents 2033C Series Owners / Technical Manual Electric Owners / Technical Manual Mitsubishi 2033C Series UPSNumber Table of Contents List of Tables IiiSingle Line Diagram UPS on Maintenance Bypass Operation List of FiguresHow to use this Manual Important Safety Instructions Retain These Instructions Electric Owners / Technical Manual IntroductionMitsubishi 2033C Series UPS Electric Owners / Technical Manual General Mitsubishi 2033C Series UPS Overview AC input User supplied Single Line Diagram Battery Operation Transfer of load from inverter to maintenance bypass Transfer of load from maintenance bypass to inverter5a UPS Parts Location7.5-20kVA SWM RYDR-X Relay PCB RYDR-X board Signal I/F on RYDR-X board Figure LCD Touch Panel Monitor DisplayExternal contact signal terminal block Reset switch for Service Personnel onlyKVA SpecificationsUPS Cable Width Depth Height Weight Heat Loss EntryAC Output AC Input CharacteristicsBattery EnvironmentalComponent Description Component Rating @ 208V,3 phase, 60 Hz Rating of Contactors and FusesLCD Touch Panel Monitor Display and Keypad Main Menu ScreenAC Input Measurement Screen Main Menu Screen Battery Measurement ScreenMeasurement Screens AC Output Measurement ScreenElectric Owners / Technical Manual Fault Display Screen Fault Display Screen10Emergency Power Off EPO red Battery operation BAT OP. yellowAlarm Silence Silence gray 11Load on maintenance bypass MBP redExternal Signal Terminal Block OverloadTerminals 7 to 8 Load on Inverter contact Output Contacts for external alarm annunciationTerminals 11 to 12 Battery Operation contact Input Contacts for remote access of UPS Terminals 3 to 4 Battery Temp. High contact inputExternal communication connector SUB 9Pin maleMitsubishi 2033C Series UPS Installation and OperationTransportation and Installation Electric Owners / Technical ManualBattery Installation ProcedureSpace requirement for routine maintenance Minimum clearance required for ventilationMitsubishi 2033C Series UPS RED Burndy UPS Terminal Designation Input/Output Power Terminals 7.5kvA 20kVA NumberRYDR-X DC Input Power TerminalMBS C N a B C NRYDR-X MBS AC Input AC Output DC InputGrounding bar Operating Procedures UPS Start-up Procedure UPS Shutdown ProcedureEPO Emergency Power Off Procedure UPS Fault Electric Owners / Technical Manual Response to UPS FailureElectric Owners / Technical Manual Parts Replacement UPS Component PartsElectric Owners / Technical Manual Fault Codes Contact Mitsubishi Electric Automation, Inc. atMitsubishi Transfer circuit abnormal Call service engineer Mitsubishi 2033C Series UPS Warranty & Out of warranty Service Mitsubishi Electric Automation IncCustomer Information Register UPS for Warranty Address ChangeMitsubishi Electric Automation, Inc