3.3Installation Procedure
A)Note the load tolerance of the floor Refer to Table 3.2 for list of UPS weights:
TABLE 3.2 List of UPS weights
UPS Capacity (kVA) | 7.5 | 10 | 15 | 20 | 30 | 40 | 50 |
Weight (lb.) | 562 | 562 | 816 | 816 | 1235 | 1082 | 1082 |
|
|
|
|
|
|
|
|
Note: 40kVA and 50kVA UPS have batteries external to module cabinet
Please refer to the remote battery supply installation manual.
B) Minimum clearance required for ventilation
Right side | 1.0" (25 mm) (not required when sidecars are used) | |
Left side | 1.0" | (25 mm) (not required when sidecars are used) |
Back side | 7.8" | (200 mm) |
Top side | 39.4" (1000 mm) |
C)Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front | 39.4" (1000 mm) | |
Sides | 1.0" | (25 mm) |
Rear | 7.8" | (200 mm) |
D)Battery
Please refer to the following when installing and maintaining batteries:
1.Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
2.When installing or replacing batteries, install or replace with the same number and type per Table 3.3
TABLE 3.3 Type and number of battery |
| ||
| Type | Manufacturer | Number |
7.5kVA,10kVA | Power Battery Inc. | 30 | |
| Yuasa Corp. |
| |
15kVA,20kVA | Power Battery Inc. | 30 | |
| Yuasa Corp. |
| |
30kVA | Power Battery Inc. | 30 | |
| Yuasa Corp. |
| |
| Yuasa Corp. |
| |
40kVA,50kVA |
|
|
|