RuggedCom RS910L manual Fiber Optic Ethernet Ports, 100FX Mtrj connector

Page 21

Table 5 - RJ45 Ethernet port pin-out

NOTE: RuggedCom does not recommend the use of CAT-5 (10/100Base-TX communications) cabling of any length for critical real-time substation automation applications. However, transient suppression circuitry is present on all copper ports to protect against damage from electrical transients and to ensure IEC 61850-3 and IEEE 1613 Class 1 conformance. This means that during the transient event communications errors or interruptions may occur but recovery is automatic.

RuggedCom also does not recommended to use these ports to interface to field devices across distances which could produce high levels of ground potential rise, (i.e. greater than 2500V) during line to ground fault conditions.

4.3 Fiber Optic Ethernet Ports

Depending on the order code of the product, the RS910L can be equipped with several different fiber optic ports. The Transmit (Tx) and Receive (Rx) connections of each port must be properly connected and matched for proper link and operation. The drawings in the following figures show each fiber optical connector style with a side and top view to allow the user to identify the proper cable connection orientation.

Figure 16: 100FX MTRJ connector

Figure 17: 100FX ST connector

Figure 15: 10FL ST connector

 

 

21

2007 RuggedCom Inc. All rights reserved

Rev100

Image 21
Contents RuggedVDSL RS910L Installation GuideTrademarks Table of Contents Table of Figures Feature Highlights Product OverviewFunctional Overview RS910L Front Panel Description RS910L Front Panel DescriptionRS910L Bottom Panel Description RS910L Bottom Panel DescriptionDin Rail Mounting InstallationAC Power Supply Wiring and Grounding Power Supply Wiring and GroundingDC Power supply wiring and grounding diagram DC Power Supply Wiring and GroundingDielectric Strength Testing Dielectric Strength TestingRS910L Failsafe Output Relay Failsafe Output WiringPin Signal RS232 Console Port WiringSerial Ports Fiber Serial Interface2 RS232/RS485/RS422 via DB9 3 RS232/RS485/RS422 via RJ45 Pin RS232 ModeRJ45 Port pin-out 4 RS485 WiringSerial Port Transient Protection Conceptual recommended RS485 wiring diagram Ethernet Ports RJ11 Ethernet over Vdsl Port Overview Wiring Configuration & SetupPerformance RJ45 Ethernet Ports Pin SignalFiber Optic Ethernet Ports 100FX Mtrj connectorEthernet Panel Description 100FX LC connectorPower Supply Specifications Technical SpecificationsFailsafe Relay Specifications Operating EnvironmentSerial Ports RJ11 Ethernet over Vdsl Port SpecificationsCopper Ports Fiber Optic PortsCommunication Standards Ethernet PortsParameter Value Mechanical SpecificationsIEC 61850-3 Type Tests Type TestsIEC Environmental Type Tests Ieee 1613 Type TestsWarranty