RuggedCom RS910L manual Wiring, Configuration & Setup, Performance

Page 19

4.1.2 Wiring

VDSL typically operates over 2-wire CAT-3 wiring; however, other categorized or uncategorized twisted-pair wiring will work although the performance will vary depending on the distance and cable characteristics. It is important that the wiring used does not have any open leads (also known as bridged taps or drop-lines) along its length because this will impact performance by degrading the signal.

4.1.3 Configuration & Setup

1.Log into the RuggedSwitch Operating System.

2.Highlight Ethernet Ports and press Enter.

3.Highlight Configure/View EoVDSL Parameters and press Enter. This will take you to the EoVDSL Parameters screen. Press Enter again.

4.Highlight Mode and press Enter.

5.Either press the Up or Down arrow to select either Master or Slave. Press Enter.

6.Press Control and A together to apply the changes.

Once configured as master and slave and connected together, the units will then attempt to achieve the maximum speed based on the line length and conditions. The unit’s link LED may flash on and off several times before settling on a final link speed and declaring the port up. Please see the Rugged Operating System (ROS) Software User Guide for detailed software configuration options.

4.1.4 Performance

On 24 American Wire Gauge (AWG) Polyethylene Insulated Cable (PIC) twisted-pair the following performance is typical:

Distance

Distance

Downstream/Upstream

Time to Achieve Port Up

[km]

[feet]

[Mbps]

[Seconds]

0.5

1600

35.00

15

0.6

2000

30.00

30

0.7

2300

25.00

45

0.8

3000

20.00

60

1.0

3300

15.00

75

1.3

4300

10.00

90

1.7

5600

5.00

105

2.0

6600

2.50

120

2.5

8200

1.00

135

Table 4 - Typical Performance on 24 AWG PIC twisted-pair

 

19

2007 RuggedCom Inc. All rights reserved

Rev100

Image 19
Contents RuggedVDSL RS910L Installation GuideTrademarks Table of Contents Table of Figures Product Overview Feature HighlightsFunctional Overview RS910L Front Panel Description RS910L Front Panel DescriptionRS910L Bottom Panel Description RS910L Bottom Panel DescriptionDin Rail Mounting InstallationAC Power Supply Wiring and Grounding Power Supply Wiring and GroundingDC Power supply wiring and grounding diagram DC Power Supply Wiring and GroundingDielectric Strength Testing Dielectric Strength TestingRS910L Failsafe Output Relay Failsafe Output WiringPin Signal RS232 Console Port WiringFiber Serial Interface Serial Ports2 RS232/RS485/RS422 via DB9 3 RS232/RS485/RS422 via RJ45 Pin RS232 Mode RJ45 Port pin-out 4 RS485 WiringSerial Port Transient Protection Conceptual recommended RS485 wiring diagramRJ11 Ethernet over Vdsl Port Ethernet PortsOverview Configuration & Setup WiringPerformance RJ45 Ethernet Ports Pin SignalFiber Optic Ethernet Ports 100FX Mtrj connectorEthernet Panel Description 100FX LC connectorOperating Environment Technical SpecificationsPower Supply Specifications Failsafe Relay SpecificationsFiber Optic Ports RJ11 Ethernet over Vdsl Port SpecificationsSerial Ports Copper PortsCommunication Standards Ethernet PortsParameter Value Mechanical SpecificationsIEC 61850-3 Type Tests Type TestsIEC Environmental Type Tests Ieee 1613 Type TestsWarranty