RuggedCom RS910L manual IEC 61850-3 Type Tests

Page 27

6 Type Tests

6.1 IEC 61850-3 Type Tests

Test

IEC 61000-4-2 IEC 61000-4-3

IEC 61000-4-4

IEC 61000-4-5

IEC 61000-4-6

IEC 61000-4-8 IEC 61000-4-29

IEC 61000-4-11

IEC 61000-4-12

IEC 61000-4-16

IEC 61000-4-17

IEC 60255-5

IEC 60255-5

 

Description

 

 

Test Levels

 

 

 

 

 

 

 

 

 

ESD

Enclosure Contact

 

 

+/- 8kV

 

 

 

 

 

 

 

Enclosure Air

 

 

+/- 15kV

 

 

 

 

 

 

 

 

 

 

 

Radiated RFI

Enclosure ports

 

 

20 V/m

 

 

Signal ports

 

 

+/- 4kV @ 2.5kHz

 

Burst (Fast

D.C. Power ports

 

 

+/- 4kV

 

Transient)

A.C. Power ports

 

 

+/- 4kV

 

 

Earth ground ports

 

 

+/- 4kV

 

 

 

 

 

 

 

Signal ports

 

+/- 4kV line-to-earth, +/- 2kV line-to-

 

 

 

 

line

 

 

 

 

 

 

Surge

D.C. Power ports

 

+/- 2kV line-to-earth, +/- 1kV line-to-

 

 

 

line

 

 

 

 

 

 

 

A.C. Power ports

 

+/- 4kV line-to-earth, +/- 2kV line-to-

 

 

 

 

line

 

 

 

 

 

 

 

Signal ports

 

 

10V

 

Induced

D.C Power ports

 

 

10V

 

(Conducted) RFI

A.C. Power ports

 

 

10V

 

 

Earth ground ports

 

 

10V

 

Magnetic Field

Enclosure ports

 

40 A/m continuous, 1000 A/m for 1 s

 

 

D.C. Power ports

 

30% for 0.1s, 60% for 0.1s, 100% for

 

 

 

 

0.05s

 

Voltage Dips &

 

 

 

 

 

 

30% for 1 period, 60% for 50 periods

 

Interrupts

 

 

 

A.C. Power ports

 

100% for 5 periods, 100% for 50

 

 

 

 

 

 

 

 

periods2

 

 

Signal ports

 

2.5kV common, 1kV differential mode

 

 

 

 

@ 1MHz

 

 

 

 

 

 

Damped

D.C. Power ports

 

2.5kV common, 1kV differential mode

 

Oscillatory

 

 

@ 1MHz

 

 

 

 

 

 

A.C. Power ports

 

2.5kV common, 1kV differential mode

 

 

 

 

@ 1MHz

 

 

 

 

 

 

Mains Frequency

Signal ports

 

30V Continuous, 300V for 1s

 

Voltage

D.C. Power ports

 

30V Continuous, 300V for 1s

 

Ripple on D.C.

D.C. Power ports

 

 

10%

 

 

Power Supply

 

 

 

 

 

 

 

 

 

 

Dielectric

Signal ports

 

2kVac

(Fail-Safe Relay output)

 

D.C. Power ports

 

 

2kVac

 

Strength

 

 

 

A.C. Power ports

 

 

2kVac

 

 

 

 

 

 

Signal ports

 

5kV

(Fail-Safe Relay output)

 

H.V. Impulse

D.C. Power ports

 

 

5kV

 

 

A.C. Power ports

 

 

5kV

 

 

 

 

 

 

 

Severity

Levels

4

4 x x 4 4 4

4

3

4

3

3

3

3

N/A

N/A

N/A

N/A

3

3

3

4

4

3

N/A

N/A

N/A

N/A

N/A

N/A

Table 16 - IEC 61850-3 Type Tests

27

2007 RuggedCom Inc. All rights reserved

Rev100

Image 27
Contents RuggedVDSL RS910L Installation GuideTrademarks Table of Contents Table of Figures Feature Highlights Product OverviewFunctional Overview RS910L Front Panel Description RS910L Front Panel DescriptionRS910L Bottom Panel Description RS910L Bottom Panel DescriptionDin Rail Mounting InstallationAC Power Supply Wiring and Grounding Power Supply Wiring and GroundingDC Power supply wiring and grounding diagram DC Power Supply Wiring and GroundingDielectric Strength Testing Dielectric Strength TestingRS910L Failsafe Output Relay Failsafe Output WiringPin Signal RS232 Console Port WiringSerial Ports Fiber Serial Interface2 RS232/RS485/RS422 via DB9 3 RS232/RS485/RS422 via RJ45 Pin RS232 ModeRJ45 Port pin-out 4 RS485 WiringSerial Port Transient Protection Conceptual recommended RS485 wiring diagramEthernet Ports RJ11 Ethernet over Vdsl PortOverview Wiring Configuration & SetupPerformance RJ45 Ethernet Ports Pin SignalFiber Optic Ethernet Ports 100FX Mtrj connectorEthernet Panel Description 100FX LC connectorOperating Environment Technical SpecificationsPower Supply Specifications Failsafe Relay Specifications Fiber Optic Ports RJ11 Ethernet over Vdsl Port Specifications Serial Ports Copper PortsCommunication Standards Ethernet PortsParameter Value Mechanical SpecificationsIEC 61850-3 Type Tests Type TestsIEC Environmental Type Tests Ieee 1613 Type TestsWarranty