5

Technical Specifications

 

5.1

Operating Environment

 

 

 

 

 

 

 

 

Parameter

 

Range

Comments

 

 

 

 

Ambient Temperature as

Ambient Operating Temperature

 

-40 to 85°C

measured from a 30 cm radius

 

surrounding the center of the

 

 

 

 

 

 

 

 

RS910 enclosure.

Ambient Storage Temperature

 

-40 to 85°C

 

Ambient Relative Humidity

 

5% to 95%

Non-condensing

Table 6 - Operating Environment

5.2 Power Supply Specifications

Power Supply Type

12 – 24 VDC

24VDC

48VDC

HI (125/250 VDC) 1 HI (110/230 VAC) 1

Minimum

Input

10VDC

18VDC

36VDC

88VDC

85VAC

Maximum

Input

36VDC

36VDC

72VDC

300VDC

265VAC

Fuse

Rating

3.15(T)

3.15(T)

3.15(T)

3.15(T)

Isolation

1.5kV DC

1.5kV DC

1.5kV DC

4 kV AC 5.5

kV DC

Maximum Power

Consumption

10W

Table 7 - Power Supply Specifications

NOTES:

1.This is the same power supply for both AC and DC.

2.(F) Denotes fast-acting fuse, (T) denotes time-delay fuse.

3.For continued protection against risk of fire, replace only with same type and rating of fuse.

5.3 Failsafe Relay Specifications

Load Circuit

 

SELV

 

 

 

 

MAX operating Voltage

30VDC

 

30 VAC

 

 

 

 

MAX operating Current

1A

 

0.5A

 

 

 

 

Isolation (between coil and contacts)

 

 

1800 Vrms

 

 

 

 

TNV-2

80VDC

0.3A

Table 8 - Failsafe Relay Specifications

 

23

2007 RuggedCom Inc. All rights reserved

Rev100

Image 23
Contents RuggedVDSL RS910L Installation GuideTrademarks Table of Contents Table of Figures Functional Overview Feature HighlightsProduct Overview RS910L Front Panel Description RS910L Front Panel DescriptionRS910L Bottom Panel Description RS910L Bottom Panel DescriptionDin Rail Mounting InstallationAC Power Supply Wiring and Grounding Power Supply Wiring and GroundingDC Power supply wiring and grounding diagram DC Power Supply Wiring and GroundingDielectric Strength Testing Dielectric Strength TestingRS910L Failsafe Output Relay Failsafe Output WiringPin Signal RS232 Console Port Wiring2 RS232/RS485/RS422 via DB9 Serial PortsFiber Serial Interface 3 RS232/RS485/RS422 via RJ45 Pin RS232 ModeRJ45 Port pin-out 4 RS485 WiringSerial Port Transient Protection Conceptual recommended RS485 wiring diagramOverview Ethernet PortsRJ11 Ethernet over Vdsl Port Performance WiringConfiguration & Setup RJ45 Ethernet Ports Pin SignalFiber Optic Ethernet Ports 100FX Mtrj connectorEthernet Panel Description 100FX LC connectorOperating Environment Technical SpecificationsPower Supply Specifications Failsafe Relay SpecificationsFiber Optic Ports RJ11 Ethernet over Vdsl Port SpecificationsSerial Ports Copper PortsCommunication Standards Ethernet PortsParameter Value Mechanical SpecificationsIEC 61850-3 Type Tests Type TestsIEC Environmental Type Tests Ieee 1613 Type TestsWarranty