Quantum 890 USE 155 manual Specifications, Power Parameter Specification

Page 16

Modbus to Ethernet Bridge

1.4Specifications

Table 2 Power

Parameter

Specification

Operating Power, Nominal

12 or 24 V dc

Operating Power Range

9 ... 30 V dc

Maximum Power Drain

3 W

Connection

Screw terminals

Fuse

External, supplied by customer.

 

Fuse value according to supply voltage

 

(see Maximum Power Drain)

 

 

Grounding

Screw terminals provided for power ground

 

and safety (Earth) ground

Table 3 Environmental

Parameter

Reference

Limits

Temperature, Operating

IEC 68±2±14

0...60_ C ambient

Humidity, Operating

IEC 68±2±3

20 ... 90% RH, non±condensing

Table 4 Ethernet Interface

Parameter

Specification

Protocol

Ethernet v2 encapsulation

 

TCP/IP Version 4

Connector

RJ45 connector for 10baseT cable

Table 5 Serial Interface

Parameter

Specification

Modbus Protocol

RTU or ASCII

Serial Protocol

Switch selectable, RS±232 or RS±485

 

Supports RS±232 RTS/CTS handshaking

 

RS±485 setting supports RS±422 devices

 

Supports 2±wire and 4±wire RS±485

 

Supports up to 16 RS±485 devices

Baud Rate

300 ... 38400 +/± 2%

Connector

RJ45 connector, screw terminals

 

RJ45 port connects to Modicon M1, Compact, 984 Slot Mount

 

controllers by direct cable. Cable adapters and adapter kits

 

are available for other products.

16

Image 16
Contents Modicon Page Breite 185 mm Höhe 230 mm Breite 178 mm Höhe 216 mm Page Preface Data, Illustrations, AlterationsPage Contents Using Panel Software GlossaryModbus to Ethernet Bridge CEV 300 Introducing the Modbus to Ethernet Bridge Bridge ApplicationsOverview Installation and Configuration Bridging Between Multiple Modbus Networks EthernetMapping for a Modbus Master Mapping Modbus and IP AddressesMapping for a Modbus Slave Modbus to Ethernet Bridge Front Panel Layout Modbus EthernetComponent Name Purpose Specifications Power Parameter SpecificationAgency Approval Parameter Specification Page Installing the Bridge Hardware Mounting the Bridge on the DIN Rail Before You Install the BridgeMounting the Bridge Connecting the Power Wiring Connecting the Power WiringConnecting the Serial Cable RJ45 Port Connecting the Serial Cable RJ45 PortCompatible Modbus Devices and Cables TSX NoteModbus Cable Pinouts References in this figure are to the devices listed in onDB to RJ45 Adapter Kits DB9M 110 XCA 203 ±Wire Connecting the Serial Cable Wiring TerminalsRS±485 RS±485 / RS±422 Setting the Serial Port Switch Setting the Serial Port SwitchConnecting the Ethernet Cable Connecting the Ethernet CableConfiguring the Bridge Safety Configuration OverviewBefore You Start Connecting by the RS±232 Port Example RS±232 Serial Terminal Emulator PropertiesConnecting by Telnet IP Address Not Assigned Telnet Host RequirementConnecting by Telnet IP Address Assigned Example Telnet ConnectionConfiguration Menu Using the Configuration MenuModbus Master Device Additional Menu Items Configuration Options 1 Viewing and Changing Configuration ParametersCommands Default settings, Save, Quit without save Retaining the Current ValueOption 1 Network/IP Settings IP AddressSet Gateway IP Address Set NetmaskConfiguring the Bridge Option 2 Serial and Mode Settings Attached DeviceSerial Protocol Interface TypeRTS/CTS Mode Option 3 Modem Control SettingsExample Option 4 Advanced Modbus Protocol Settings Slave AddressMessage Timeout Character TimeoutAllow Modbus Broadcasts How the Address Mapping Works Option 5 Unit ID to IP Address Mapping TableExample Address Mapping Entering New Address Mapping Exiting the Mapping MenuAdding a New Map Entry Deleting a Map EntryPage Using Panel Software Software Versions Using Concept or ModsoftModbus Slave Address Using Other Software Intellution FIX MMIWinTech Modscan Worderware MMIPage Glossary Default gateway FieldFrame Framing typesInternet LayerMAC Address NetworkSwitch RepeaterRouter ServerUTP WinsockPage United States France Germany